Operating instructions
15
Initial start−up, inspection and maintenance
Further details regarding the individual steps (cont.)
Cleaning the multiple level electrode
1. Remove electrodeA.
2. Clean electrode tipsC.
3. Clean the sealing faces and use a
new gasketB.
4. Install the electrodes and carry out
a safety test in line with the
manufacturer’s instructions.
5. Retighten new gaskets after
commissioning.
Cleaning the water level indicator
1. Blow out the water level indicator.
2. Remove upper plugA, and clean
the water level indicator with a
brush.
5692729 GB
A
B
C