Operating instructions

27
Appendix
Specification
Steam output
*1
kg/h 260 435 700
Rated output kW 170 285 460
Flue gas values
*2
Temperature
at rated output
at partial load
ºC
ºC
200
130
200
130
200
130
CE designation CE0035
*1
at a feed water temperature of 80ºC.
*2
Values for calculating the size of the flue system to DIN4750 based on 13% CO
2
for
fuel oilEL and 10
% CO
2
for natural gas.
Flue gas temperature measured at 20ºC combustion air temperature.
5692729 GB