Operating instructions

134
Components
Function extension 0−10V (cont.)
Boiler system with
Function Condition at Vitotronic
Vitotronic100 Demands to the boiler
in accordance with the
set operating mode and
set temperature; the
0−10 V hook−up creates
an additional set value
Code "01:1"
Multi−boiler system with
external cascade
Function Preconditions
Vitotronic100 with
enable command via
0−10 V signal
Boiler control via 0−10 V
hook−up:
0 to 1V
H Boiler blocked
H Butterfly valve closed
H Boiler circuit or shunt
pump OFF
1 to 10V
H Boiler water
temperature default
H Enable boiler; the
boiler is held at its
minimum
temperature
H Butterfly valve open
H Boiler circuit or shunt
pump enabled
Code "01:3" at
Vitotronic100
Note
On the lead boiler, the
voltage must be higher
than 1V.
Vitotronic100 with
0−10V signal and enable
via switching outputaVH
The boiler is enabled;
the boiler is held at its
minimum temperature
1−10V additional
temperature default
H Code "01:3" at
Vitotronic100
H Contact at terminal2
and 3 of plugaVH
closed
Note
This contact must
always be closed on the
lead boiler.
5862730GB