Operating instructions

147
Coding
Code2 (cont.)
Coding in the delivered condition
Possible change
DHW
55:0 Cylinder heating,
hysteresis±2.5K
55:1 Adaptive cylinder heating
active (speed of temp. rise
for cylinder temperature is
taken into account during
DHW heating)
55:2 Cylinder temperature
control with 2cylinder
temperature sensors
55:3 Cylinder temperature
control
cylinder storage system
56:0 Setting range for DHW
temperature 10 to 60ºC
56:1 DHW temperature setting
range 10 to 95ºC
Notes
H Observe the max.
permissible DHW
temperature
H Change control
thermostat"R"
58:0 Without auxiliary function
for DHW heating
58:1
to
58
:95
Input of a secondset DHW
value; adjustable from
1 to 95ºC (observe coding
address"56" and section
"Additional function" on
page124)
59:0 Cylinder heating:
Starting point 2.5KK
Shutdown point+2.5K
59:1
to
59:10
Starting point adjustable
from 1 to 10K below the set
value
5A:0 No function 5A:1 Flow temperature demand
of DHW cylinder is
maximum system value
60:20 During DHW heating, boiler
water temperature is max.
20K higher than set DHW
temperature
60:10
to
60:50
The difference between the
boiler water temperature
and the set DHW
temperature is adjustable
from 10 to 50K
5862730GB