Coding
Code2 (cont.)
Coding in the delivered condition
Possible change
DHW (cont.)
61:1 The cylinder primary pump
starts immediately
61:0 The cylinder primary pump
will be switched ON subject
to the boiler water
temperature
62:10 The cylinder primary pump
will run on for a max. of
62:0 Cylinder primary pump
without run−on
10min
62:1
to
62
:15
Run−on time adjustable
from 1 to 15min
63:0 Without auxiliary function
for DHW heating
63:1
Additional function:
1×daily
g
63:2
to
63
:14
every 2days
to
every 14days
63:15 2×daily
67:40 With Vitosolic:
Third set DHW temperature
67:0 Without a third set DHW
temperature
p
at 40ºC. Reheating will be
suppressed above the
selected temperature. The
DHW cylinder is heated
exclusively by the solar
heating system.
67:1
to
67
:95
Input of a third set DHW
value; adjustable from
1 to 95ºC (subject to the
setting of coding
address"56")
68:8 With 2cylinder temperature
sensors (coding "55
:2"):
cylinder heating switch−off
point with set value×0.8
68:2
to
68
:10
Factor adjustable
from 0.2 to 1;
1step¢0.1
69:7 With 2cylinder temperature
sensors (coding "55
:2"):
cylinder heating starting
point with set value×0.7
69:1
to
69
:9
Factor adjustable
from 0.1 to 0.9;
1step¢0.1
5862730GB