Operating instructions

43
Heating system designs
System version 14 (cont.)
Possible applications
The cascade and cylinder control
must be provided by a higher control
unit.
The Vitocrossal 300 (lead boiler) and
the next low temperature boiler
should be operated via a
weather−compensated control
system with modulating boiler water
temperature and load−dependent
sequential control  two−stage or
modulating burners are regulated.
Vitocrossal 300 is equipped with two
return connectors. The heating
circuits with the higher return
temperature are connected to the
upper return connector and those
with lower return temperatures to
the lower return connector. Note:
connect at least 15% of the rated
output to the lower return connector.
The ThermControl temperature
sensor of the low temperature boiler
controls the motorised butterfly
valve and must reduce the boiler
water volume flow of the low
temperature boiler during the
start−up phase (e.g. during
commissioning or after night or
weekend shutdown).
5862730GB