Operating instructions

48
Heating system designs
System version 16 (cont.)
Codes must be set on every Vitotronic 100.
Required coding
01 : 2 Multi−boiler system with cascade control via LON BUS
01 : 3 Multi−boiler system with external cascade control via switching
contacts
02 : 2 Modulating burner operation
*1
03 : 1 Only with Vitotronic 100 for Vitoplex:
Oil fired operation (irreversible)
*1
0d : 0 Only with Vitotronic 100 for Vitocrossal300:
Without Therm−Control
4d : 3 Only with Vitotronic 100 for Vitoplex:
Boiler circuit pump with butterfly valve function on plug sL
Automatic changeover
4A: 1 Only with Vitotronic 100 for Vitoplex:
Connecting the Therm−Control temperature sensor to plug aJA
*1
If required.
5862730GB