Checking the condensate drain and cleaning the siphon
A
B
1. Check that the condensate can drain
freely at the siphon.
2.
Remove all hoses from siphon A.
3.
Release locking tabs at opening B
from underneath and remove siphon
A
upwards.
4.
Clean siphon A and reinstall.
5. Refit all hoses. Secure drain hose
with cable ties.
6.
Fill siphon A with water. by pouring
about 0.3 l of water into the combus-
tion chamber.