If this happens, shut down the inverter with the main switch (fig. 5 3,
page 4).
Check that the inverter is sufficiently ventilated and that the ventilation
grilles are unimpeded.
Wait 5 – 10 minutes and switch the inverter on again without any electric
consumers.
When operating the inverter at high load for lengthy periods, it is advisable to
start the engine in order to recharge the vehicle battery.
10.3 Configuring the inverter
You can adjust the device using the DIP switch (fig. 5 1, page 4).
Setting the mains voltage
You can set the mains voltage using the S1 and S2 dip switches.
Setting the mains frequency
!
You can set the mains frequency using the S3 dip switch.
DIP switch
Mains voltage S1 S2
200 V Off Off
220 V On Off
230 V Off On
240 V On On
WARNING! Danger of electrocution
Only adjust the S3 DIP switch when the respective frequency for
the output voltage should be used.
DIP switch
Net frequency S3
50 Hz Off
60 Hz On