Product Brochure
How to Order
• Heating element should be embedded within a
minimum 3/8” thick layer of modified thinset or self-
leveling underlayment.
• Heating cable should be installed within 1” to 1.5”
from the top of the flooring surface.
• Multiple heating cables can be wired to a control,
as long as they total less than 15 amps (the limit of
the controller).
• Multiple heating cables are never wired to each
other in series (parallel wiring required). The
non-heating leads from each heating cable need to
hook up to the controller and be wired in parallel.
• Do not install under permanent fixtures.
• Do not install within 4” of the toilet wax ring.
• Entire heating section and splices need to be
embedded in thinset or self-leveling underlayment
to prevent overheating and premature failure.
• Do not shorten the heating cable. Do NOT cut the
heating cable. Only the non-heating cold leads can
be shortened.
• Do not run a power lead or sensor wire across a
warming cable.
Installation Information
Simply draw a floor plan sketch of your project
(including dimensions) and let us know if you have a
preference between fixing strips and Prodeso.
Send it to sales@warmlyyours.com. Then
WarmlyYours’s skilled engineers will create a free
SmartPlan™ custom installation plan based on your
drawing, typically in as little as 1 business day.
After you receive your SmartPlan™, just verify the
correct dimensions before placing your order with your
WarmlyYours account manager.
• Do not fold or position the heating cable so that it overlaps
itself or other warming cables (this could lead to
dangerous overheating).
• Do not connect the heating cable to the power supply for
testing before it is embedded (this could lead to
dangerous overheating). Testing is only done with a
digital ohm meter.
• Cable spacing (ranging from 3” at a minimum to 5” at
a maximum) will impact how many square feet of heating
coverage can be installed on a single circuit. For a 120V
circuit, heating coverage would range from 120 to 200 sq.
ft. For a 240V circuit, this range would be from 240 to 400
sq. ft.
• TempZone Cable should be installed with a floor sensor.
All WarmlyYours nSpiration Series thermostats come with a
floor sensor.
Layout TempZone™ Cable
with Fixing Strips or the
Prodeso Membrane
Secure the Included
Floor Sensor
Apply Thinset or SLC (⁄”
thick minimum)
Install
Flooring
1 2 3 4
1
2
3
4 Simple Steps to Install