User`s manual

WATLOW DIN-A-MITE Style C User's Manual
7
ç
3
WARNING:
Only authorized and
qualified personnel
should be allowed to
install and perform
preventive and corrective
maintenance on this unit.
Failure to follow this
guideline could result in
damage to equipment,
and personal injury or
death.
5
WARNING:
Hot surface, do not touch
the heat sink. Failure to
follow this guideline
could result in personal
injury.
ç
Mount the cooling fins
vertically.
Unit Dimensions - Rail-Mounted
5
ç
3
Ground
wire
entry
146 mm
(5.74 in)
83 mm
(3.25 in)
Top
142 mm (5.59 in)
131 mm
(5.17 in)
146 mm (5.74 in)
102 mm (4.0 in)
Front panel is touch-safe, no clearance is required.
102 mm (4.0 in) clearance for air flow and wire bending radius
102 mm (4.0 in) clearance for air flow and wire bending radius
150 mm
(5.89 in)
Rail Release Tab
(pull down)
44 mm
(1.73 in)
57 mm
(2.26 in)
127 mm
(5.00 in)
79 mm
(3.10 in)
102 mm (4.0 in) minimum
Side
Front
138 mm
(5.45 in)
54 mm (2.11 in)
46 mm (1.81 in)
38 mm (1.51 in)
123
456
48 mm
(1.89 in)
Allowance for M4
(#8 Fastener)
Allowance for M4
(#8 Fastener)
DIN-EN 50022
35 by 7.5 mm rail
(clipping distance =
34.7 to 35.3 mm
[1.366 to 1.390 in])
87 mm