Instruction Manual

12
3.3.2 BAUD RATE SELECTION
WARNING - TURN OFF POWER BEFORE CHANGING BAUD
RATE
Baud rate is selected by positioning a selector jumper on J1 on the main circuit board.
The position farthest from the card cage is 600 baud and the positions are then as
follows:
600
300
2400
4800
1200
9600
Units are normally shipped from the factory with the baud rate set at 2400 baud. This
rate is recommended for most applications.
3.4 AC POWER INPUT
WARNING - POWER MUST BE 110VAC, 60HZ
The ANAFAZE 8 PID requires 110VAC at 60Hz for power input. A power on LED will
indicate when power is applied.
WARNING - HIGH VOLTAGE MAY BE PRESENT WHEN
POWER IS DISCONNECTED
3.4.2 POWER CONNECTIONS
The power must be connected according to the terminal labels. The abbreviations are:
GND Third wire ground -- normally Green wire
NEU 110VAC Neutral -- normally white wire
HOT 110VAC Hot -- normally black wire
3.4.3 POWER FUSE
A 1/4 amp fuse is located beneath the circuit board near the power terminals. Power to
the ANAFAZE 8 PID must be removed before changing the fuse.