Watlow EZ-ZONE
®
PM Integrated Controller 97 Chapter 6 Setup Page
Setup Page
Dis-
play
Parameter Name
Description
Range Default
Modbus Rela-
tive
Address
CIP
Class
Instance
Attribute
hex (dec)
Pro-
fibus
Index
Param-
eter ID
Data
Type
&
Read/
Write
[poti]
[Poti]
Global
Power Off Time
If profile is running and
power is lost, profile
will resume where it
left off provided time
set has not expired pri-
or to power restoration.
0 to 9999 seconds 0 Instance 1
Map 1 Map 2
- - - - 4484
7A (122)
1
0x49 (73)
- - - - 22073 uint
RWE
[sutb]
[Sutb]
Global
Synchronized Variable
Time Base
Used to acquire tighter
accuracy when running
a profile. A setting of
+0.01 would equate to
approximately +9 sec-
onds/day (faster) where
a setting of -0.01 would
equate to approximately
-9 seconds/day (slower).
-2.00 to 2.00 Percent 0.00 - - - - - - - - - - - - - - - - float
RWE
[C;led]
[C.LEd]
Global
Communications LED
Action
Turns comms LED on or
off for selected comms
ports.
[Con1] Comm port 1 (1189)
[Con2] Comm port 2 (1190)
[both] Comm port 1 and 2
(13)
[`off] Off (62)
both Instance 1
Map 1 Map 2
1856 2326
0x6A (103)
1
0x0E (14)
- - - - 3014 uint
RWES
[2one]
[Zone]
Global
Zone
Turns Zone LED on or
off based on selection.
[`off] Off (62)
[``on] On (63)
On Instance 1
Map 1 Map 2
- - - - 2350
0x6A (103)
1
0x1A (26)
- - - - 3026 uint
RWES
[Chan]
[Chan]
Global
Channel
Turns Channel LED on
or off based on selection.
[`off] Off (62)
[``on] On (63)
On Instance 1
Map 1 Map 2
- - - - 2352
0x6A (103)
1
0x1B (27)
- - - - 3027 uint
RWES
[d;prs]
[dPrS]
Global
Display Pairs
Defines the number of
Display Pairs.
1 to 10 2 Instance 1
Map 1 Map 2
- - - - 2354
0x6A (103)
1
0x1C (28)
- - - - 3028 uint
RWES
[`d;ti]
[ d.ti]
Global
Display Time
Time delay in toggling
between Display Pairs.
0 to 60 0 Instance 1
Map 1 Map 2
- - - - 2356
0x6A (103)
1
0x1D (29)
- - - - 3029 uint
RWES
[USr;S]
[USr.S]
Global
User Settings Save
Save all of this control-
ler's settings to the
selected set.
[SEt1] User Set 1 (101)
[SEt2] User Set 2 (102)
[none] None (61)
None
Instance 1
Map 1 Map 2
26 26
0x(101)
1
0xE (14)
118 1014 uint
RWE
[USr;r]
[USr.r]
Global
User Settings Restore
Replace all of this con-
troller's settings with
another set.
[FCty] Factory (31)
[none] None (61)
[SEt1] User Set 1 (101)
[SEt2] User Set 2 (102)
None
Instance 1
Map 1 Map 2
24 24
0x65
(101)
1
0xD (13)
117 1013 uint
RWE
Note:
Some values will be rounded off to fit in the four-character display. Full values can be read
with other interfaces.
R: Read
W: Write
E: EEPROM
S: User