Owner manual

Watlow EZ-ZONE
®
PM Integrated Controller 99 Chapter 6 Setup Page
Setup Page
Dis-
play
Parameter Name
Description
Range Default
Modbus Rela-
tive
Address
CIP
Class
Instance
Attribute
hex (dec)
Pro-
fibus
Index
Param-
eter ID
Data
Type
&
Read/
Write
[Map]
[ Map]
Communications (1)
Data Map
If set to 1 the control will
use PM legacy mapping.
If set to 2 the control
will use new mapping to
accommodate new func-
tions.
1 to 2 1 if 9
th
digit
of part
number
is a D or
1 other-
wise, 2.
- - - - - - - - - - - - 17059 uint
RWE
[`nU;S]
[ nV.S]
Communications (1)
Non-Volatile Save
If set to Yes all values
written to the control
will be saved in EE-
PROM. The EEPROM
allows for approximately
one million writes.
[`yes] Yes (106)
[``no] No (59)
Yes Instance 1
Map 1 Map 2
2494 2974
0x96 (150)
1
8
198 17051 uint
RWE
[`Ad;d]
[ Ad.d]
Communications (2)
DeviceNet™ Node Ad-
dress
Set the DeviceNet™ ad-
dress for this gateway.
0 to 63
63 - - - - - - - - - - - - 17052 - - - -
[bAUd]
[bAUd]
Communications (2)
Baud Rate DeviceNet™
Set the DeviceNet speed
for this gateway's com-
munications to match
the speed of the serial
network.
[`125] 125 kb (1351)
[`250] 250 kb (1352)
[`500] 500 kb (1353)
125 - - - - - - - - - - - - 17053 - - - -
[`FC;E]
[ FC.E]
Communications (2)
DeviceNet™ Quick
Connect Enable
Allows for immediate
communication with the
scanner upon power up.
[``no] No (59)
[`YES} Yes (106)
No - - - - - - - - - - - - 17054 - - - -
[P;Add]
[P.Add]
Communications (2)
Profibus Node Address
Set the Profibus address
for this control.
0 to 126
126 - - - - - - - - - - - - 17060 - - - -
[a;loc]
[A.Loc]
Communications (2)
Profibus Address Lock
When set to yes will
not allow address to be
changed using software.
Can be changed from
front panel.
[``no] No (59)
[`YES} Yes (106)
No - - - - - - - - - - - - 17061 - - - -
[iP;M]
[iP.M]
Communications (2)
IP Address Mode
Select DHCP to let a
DHCP server assign an
address to this module.
[dhCP] DHCP (1281)
[F;Add] Fixed Address (1284)
DHCP - - - - - - - - - - - - 17012 - - - -
[iP;F1]
[ip.F1]
Communications (2)
IP Fixed Address Part
1
Set the IP address of this
module. Each device on
the network must have a
unique address.
0 to 255 169 - - - - - - - - - - - - 17014 - - - -
Note:
Some values will be rounded off to fit in the four-character display. Full values can be read
with other interfaces.
R: Read
W: Write
E: EEPROM
S: User
Set