Owner manual

Watlow EZ-ZONE
®
PM Integrated Controller 104 Chapter 7 Profiling Page
2. Press the Up ¿ or Down ¯ key to change to another profile (1 to 4).
3. Press the Advance Key
to move to the selected profiles first step.
4. Press the Up ¿ or Down ¯ keys to move through and select the step type.
5. Press the Advance Key
to move through the selected step settings.
6. Press the Up ¿ or Down ¯ keys to change the steps settings.
7. Press the Infinity Key ˆ at any time to return to the step number prompt.
8. Press the Infinity Key ˆ again to return to the profile number prompt.
9. From any point press and hold the Infinity Key ˆ for two seconds to return to the Home Page.
If using EZ-ZONE Configurator software, simply click on the plus sign next to Profiles in the left hand col-
umn, as shown in the screen shot below.
Notice in the screen shot to the right some fields or parameters are not selectable (grayed out) based on the
Step Type that is selected.
Starting a Profile
There are several ways to start a profile. Some of the examples that follow requires that certain optional
hardware be available on the control. If you are uncertain as to how your control is equipped, compare the
part number of your control to the "Ordering Information" page found in the Appendix of this Users Guide.
Ways to start a profile:
- Function Key
- Digital Input
- Profile Request
Configuring the Function Key
to Start and Stop a Profile
1. Navigate to the Setup
Page and then the Func-
tion menu. From the
Home Page, press and
hold the ¿ or Down ¯
key for approximately six
seconds where the upper
display will show [``ai]
and the lower display
will show [`set].
2. Press the Up ¿ or Down
¯ key to navigate to the
Function [`fUn] menu.
3. Press the Advance Key
to enter this menu.
The upper display will
show [hig h] and the
lower display will show
[`leu] .
4. Press the Up ¿ or Down
¯ keys to select the level
that will start the profile
(high or low).
5. Press the Advance Key
to select the function. In this example, select Profile Start / Stop [p ;sts] .
6. Press the Advance Key
to select the function instance (Profile to start).
7. Return to the Home Page by pressing and holding the Infinity Key ˆ for approximately three seconds.
Note:
The state of the EZ-Function Key (high or low) is maintained with each successive push of the key.