Owner manual

Watlow EZ-ZONE
®
PM Integrated Controller 109 Chapter 7 Profiling Page
Profiling Page
Dis-
play
Parameter Name
Description
Range Default
Modbus
Relative Ad-
dress
CIP
Class
Instance
Attribute
hex (dec)
Param-
eter ID
Data
Type
&
Read/
Write
[WE;2]
[WE.2]
Step Type Parameters
Wait Event 2
When Step Type is Wait for
Event or Wait For Both, select
the event state that must
be satisfied during this step.
Note:
Wait Event 2 can be mapped
to any available digital input
(5 - 12). Navigate to the Setup
Page under the Global Menu
to find and modify Source
Instance A [`s;ia] and Source
Instance B [`s;ib].
[`oFF] Off (62)
[``on] On (63)
[nonE] None (61)
Off Instance 1
Map 1 Map 2
2588 4518
Offset to next
instance (Map
1 equals +50,
Map 2 equals
+100)
0x79 (121)
1 to 40
0xA (10)
21010 uint
RWE
[dow]
[dow]
Step Type Parameters
Day of Week
When Step Type is Wait for
Time, the profile waits until this
Day of Week along with Hours,
Minutes and Seconds time of
day is met.
[``ed] Every Day (1567)
[`wd] Week days (1566)
[`sun] Sunday (1565)
[mon] Monday (1559)
[`tue] Tuesday (1560)
[wed] Wednesday (1561)
[thUr] Thursday (1562)
[`fri] Friday (1563)
[`sat] Saturday (1564)
Sunday Instance 1
Map 1 Map 2
- - - - 4580
Offset to next
instance Map 2
equals +100)
0x79 (121)
1 to 40
0x29 (41)
21041 uint
RWE
[~~JS]
[ JS]
Step Type Parameters
Jump Step
When Step Type is Jump Loop,
this specifies which step to jump
back to. Jump Step must be a
lower step number than the cur-
rent step number.
1 to 40
0 Instance 1
Map 1 Map 2
2592 4522
Offset to next
instance (Map
1 equals +50,
Map 2 equals
+100)
0x79 (121)
1 to 40
0xC (12)
21012 uint
RWE
[~~JC]
[ JC]
Step Type Parameters
Jump Count
When Step Type is Jump Loop,
this specifies the number of
jumps to repeat. A value
of 0 creates an infinite loop.
Loops can be nested four deep.
0 to 9,999
0 Instance 1
Map 1 Map 2
2594 4524
Offset to next
instance (Map
1 equals +50,
Map 2 equals
+100)
0x79 (121)
1 to 40
0xD (13)
21013 uint
RWE
[~End]
[ End]
Step Type Parameters
End Type
When Step Type is End, this
specifies what the controller will
do when this profile ends.
[`oFF] Control Mode set to Off
(62)
[Hold] Hold last closed-loop set
point in the profile (47)
[USEr] User, reverts to previ-
ous set point (100)
Off Instance 1
Map 1 Map 2
2596 4526
Offset to next
instance (Map
1 equals +50,
Map 2 equals
+100)
0x79 (121)
1 to 40
0xE (14)
21014 uint
RWE
Note:
Some values will be rounded off to fit in the four-character display. Full values can be read with other
interfaces.
R: Read
W: Write
E: EEPROM
S: User Set