Owner manual

Watlow EZ-ZONE
®
PM Integrated Controller 160 • Chapter11Appendix
CIP Implicit O to T (Originator to Target) Assembly Structure
CIP Implicit T to O (Target to Originator) Assembly Structure
Assembly
Members
PM Assembly
Class, Instance,
Attritbute
PM
Data Type
Parameter
Parameter
Class, Instance,
Attritbute
PLC
Data Type
1 0x77, 0x01, 0x01 DINT Loop Control Mode 0x97, 0x01, 0x01 DINT
2 0x77, 0x01, 0x02 DINT Closed Loop Set Point 0x6B, 0x01, 0x01 REAL
3 0x77, 0x01, 0x03 DINT Open Loop Set Point 0x6B, 0x01, 0x02 REAL
4 0x77, 0x01, 0x04 DINT Alarm 1 - Alarm High Set Point 0x6D, 0x01, 0x01 REAL
5 0x77, 0x01, 0x05 DINT Alarm 1 - Alarm Low Set Point 0x6D, 0x01, 0x02 REAL
6 0x77, 0x01, 0x06 DINT Alarm 2 - Alarm High Set Point 0x6D, 0x02, 0x01 REAL
7 0x77, 0x01, 0x07 DINT Alarm 2 - Alarm Low Set Point 0x6D, 0x02, 0x02 REAL
8 0x77, 0x01, 0x08 DINT Alarm 3 - Alarm High Set Point 0x6D, 0x03, 0x01 REAL
9 0x77, 0x01, 0x09 DINT Alarm 3 - Alarm Low Set Point 0x6D, 0x03, 0x02 REAL
10 0x77, 0x01, 0x0A DINT Alarm 4 - Alarm High Set Point 0x6D, 0x04, 0x01 REAL
11 0x77, 0x01, 0x0B DINT Alarm 4 - Alarm Low Set Point 0x6D, 0x04, 0x02 REAL
12 0x77, 0x01, 0x0C DINT Profile Action Request 0x7A, 0x01, 0x0B DINT
13 0x77, 0x01, 0x0D DINT Profile Start 0x7A, 0x01, 0x01 DINT
14 0x77, 0x01, 0x0E DINT Heat Proportional Band 0x97, 0x01, 0x06 REAL
15 0x77, 0x01, 0x0F DINT Cool Proportional Band 0x97, 0x01, 0x07 REAL
16 0x77, 0x01, 0x10 DINT Time Integral 0x97, 0x01, 0x08 REAL
17 0x77, 0x01, 0x11 DINT Time Derivative 0x97, 0x01, 0x09 REAL
18 0x77, 0x01, 0x12 DINT Heat Hysteresis 0x97, 0x01, 0x0B REAL
19 0x77, 0x01, 0x13 DINT Cool Hysteresis 0x97, 0x01, 0x0C REAL
20 0x77, 0x01, 0x14 DINT Dead Band 0x97, 0x01, 0x0A REAL
CIP Implicit Assembly
Originator (Master) to Target (PM)
Assembly
Members
PM Assembly
Class, Instance,
Attritbute
PM
Data Type
Parameter
Parameter
Class, Instance,
Attritbute
PLC
Data Type
1 Cannot be changed Binary Device Status none DINT
2 0x77, 0x02, 0x01 DINT Analog Input 1, Analog Input Value 0x68, 0x01, 0x01 REAL
3 0x77, 0x02, 0x02 DINT Analog Input 1, Input Error 0x68, 0x01. 0x02 REAL
4 0x77, 0x02, 0x03 DINT Analog Input 2, Analog Input Value 0x68, 0x02, 0x01 REAL
5 0x77, 0x02, 0x04 DINT Analog Input 2, Input Error 0x68, 0x02, 0x02 REAL
6 0x77, 0x02, 0x05 DINT Alarm 1, Alarm State 0x6D, 0x01, 0x09 DINT
7 0x77, 0x02, 0x06 DINT Alarm 2, Alarm State 0x6D, 0x02, 0x09 DINT
8 0x77, 0x02, 0x07 DINT Alarm 3, Alarm State 0x6D, 0x03, 0x09 DINT
9 0x77, 0x02, 0x08 DINT Alarm 4, Alarm State 0x09, 0x04, 0x09 DINT
10 0x77, 0x02, 0x09 DINT Event Status 0x6E, 0x01, 0x05 DINT
11 0x77, 0x02, 0x0A DINT Event Status 0x6E, 0x02, 0x05 DINT
12 0x77, 0x02, 0x0B DINT Control Mode Active 0x97, 0x01, 0x02 DINT
13 0x77, 0x02, 0x0C DINT Heat Power 0x97, 0x01, 0x0D REAL
14 0x77, 0x02, 0x0D DINT Cool Power 0x97, 0x01, 0x0E REAL
15 0x77, 0x02, 0x0E DINT Limit State 0x70, 0x01, 0x06 DINT
16 0x77, 0x02, 0x0F DINT Profile Start 0x74, 0x01, 0x01 DINT
17 0x77, 0x02, 0x10 DINT Profile Action Request 0x74, 0x01, 0x0B DINT
18 0x77, 0x02, 0x11 DINT Current Profile 0x74, 0x01, 0x03 DINT
19 0x77, 0x02, 0x12 DINT Current Step 0x74, 0x01, 0x04 DINT
20 0x77, 0x02, 0x13 DINT Active Set Point 0x74, 0x01, 0x05 REAL
21 0x77, 0x02, 0x14 DINT Step Time Remaining 0x74, 0x01, 0x09 DINT
CIP Implicit Assembly
Target (PM) to Originator (Master)
CIP Implicit Assembly Structures