Owner manual

Watlow EZ-ZONE
®
PM Integrated Controller 54 Chapter 5 Operations Page
Operations Page
Dis-
play
Parameter name
Description
Range Default
Modbus
Relative Ad-
dress
CIP
Class
Instance
Attribute
hex (dec)
Probus
Index
Param-
eter ID
Data
Type
& Read/
Write
[``Ai]
[oPEr]
Analog Input Menu
[`Ain]
[ Ain]
Analog Input (1 to 2)
Analog Input Value
View the process value.
Note:
Ensure that the Input
Error (below) indicates
no error (61) when
reading this value us-
ing a field bus protocol.
If an error exists, the
last known value prior
to the error occurring
will be returned.
-1,999.000 to 9,999.000°F
or units
-1,128.000 to 5,537.000°C
Instance 1
Map 1 Map 2
360 360
Instance 2
Map 1 Map 2
440 450
0x68 (104)
1 to 2
1
0 4001 float
R
[`i;Er]
[ i.Er]
Analog Input (1 to 2)
Input Error
View the cause of the
most recent error. If
the
[Attn]
message is
[Er;i1]
or
[Er;i2]
, this
parameter will display
the cause of the input
error.
[nonE] None (61)
[OPEn] Open (65)
[FAiL] Fail (32)
[Shrt] Shorted (127)
[`E;M] Measurement Er-
ror (140)
[E;CAL] Bad Calibration
Data (139)
[Er;Ab] Ambient Error (9)
[E;;Rtd] RTD Error (141)
[Nsrc] Not Sourced (246)
None Instance 1
Map 1 Map 2
362 362
Instance 2
Map 1 Map 2
442 452
0x68 (104)
1 to 2
2
1 4002 uint
R
[`i;Ca]
[ i.CA]
Analog Input (1 to 2)
Calibration Offset
Offset the input reading
to compensate for lead
wire resistance or other
factors that cause the in-
put reading to vary from
the actual process value.
-1,999.000 to 9,999.000°F
or units
-1,110.555 to 5,555.000°C
0.0 Instance 1
Map 1 Map 2
382 382
Instance 2
Map 1 Map 2
462 472
0x68 (104)
1 to 2
0xC (12)
2 4012 float
RWES
[`Lnr]
[oPEr]
Linearization Menu
[`Su;A]
[ Su.A]
Linearization (1 to 2)
Source Value A
View the value of Source
A.
Source A of Lineariza-
tion 1 is connected to
Analog Input 1
Source A of Lineariza-
tion 2 is connected to
Analog Input 2
-1,999.000 to 9,999.000°F
or units
-1,128.000 to 5,537.000°C
Instance 1
Map 1 Map 2
- - - - 3566
Instance 2
Map 1 Map 2
- - - - 3636
0x86 (134)
1 to 2
4
- - - - 34004 float
R
[oFSt]
[oFSt]
Linearization (1 to 2)
Offset
Set an offset to be ap-
plied to this function's
output.
-1,999.000 to 9,999.000°F
or units
-1,128.000 to 5,537.000°C
0 Instance 1
Map 1 Map 2
- - - - 3570
Instance 2
Map 1 Map 2
- - - - 3640
0x86 (134)
1 to 2
6
- - - - 34006 float
RWES
Note:
Some values will be rounded off to fit in the four-character display. Full values can
be read with other interfaces.
R: Read
W: Write
E: EEPROM
S: User
Set