Owner manual

Watlow EZ-ZONE
®
PM Integrated Controller 55 Chapter 5 Operations Page
Operations Page
Dis-
play
Parameter name
Description
Range Default
Modbus
Relative Ad-
dress
CIP
Class
Instance
Attribute
hex (dec)
Probus
Index
Param-
eter ID
Data
Type
& Read/
Write
[``o;u]
[ o.v]
Linearization (1 to 2)
Output Value
View the value of this
function's output.
-1,999.000 to 9,999.000°F
or units
-1,128.000 to 5,537.000°C
Instance 1
Map 1 Map 2
- - - - 3572
Instance 2
Map 1 Map 2
- - - - 3642
0x86 (134)
1 to 2
7
- - - - 34007 float
R
No
Dis-
play
Linearization (1 to 2)
Output Error
View reported cause for
Linearization output
malfunction.
[none] None (61)
[open] Open (65)
[shrt] Shorted (127)
[`e;m] Measurement er-
ror (140)
[e;Cal] Bad calibration
data (139)
[er;ab] Ambient error (9)
[e;rtd] RTD error (14)
[fail] Fail (32)
[er;m] Math error (1423)
[nSrc] Not sourced (246)
[stal] Stale (1617)
[no;pr] Can't process
(1659)
None Instance 1
Map 1 Map 2
- - - - 3614
Instance 2
Map 1 Map 2
- - - - 3684
0x86 (134)
1 to 2
0x1C (28)
- - - - 34028 uint
R
[``Pu]
[oPEr]
Process Value Menu
[`Su;A]
[ Sv.A]
Process Value (1 to 2)
Source Value A
View the value of Source
A.
Linearization 1 is con-
nected to Source A of
Process Value 1
Linearization 2 is con-
nected to Source A of
Process Value 2
-1,999.000 to 9,999.000°F
or units
-1,128.000 to 5,537.000°C
Instance 1
Map 1 Map 2
- - - - 3310
Instance 2
Map 1 Map 2
- - - - 3380
0x7E (126)
1 to 2
0x10 (16)
- - - - 26016 float
R
[`Su;b]
[ Sv.b]
Process Value (1 to 2)
Source Value B
View the value of Source
B.
Linearization 2 is con-
nected to Source B of
Process Value 1
Linearization 1 is con-
nected to Source B of
Process Value 2
-1,999.000 to 9,999.000°F
or units
-1,128.000 to 5,537.000°C
Instance 1
Map 1 Map 2
- - - - 3312
Instance 2
Map 1 Map 2
- - - - 3382
0x7E (126)
1 to 2
0x11 (17)
- - - - 26017 float
R
[oFSt]
[oFSt]
Process Value (1 to 2)
Offset
Set an offset to be ap-
plied to this function's
output.
-1,999.000 to 9,999.000°F
or units
-1,128.000 to 5,537.000°C
0 Instance 1
Map 1 Map 2
- - - - 3324
Instance 2
Map 1 Map 2
- - - - 3394
0x7E (126)
1 to 2
0x17 (23)
- - - - 26023 float
RWES
Note:
Some values will be rounded off to fit in the four-character display. Full values can
be read with other interfaces.
R: Read
W: Write
E: EEPROM
S: User
Set