Owner manual

Watlow EZ-ZONE
®
PM Integrated Controller 56 Chapter 5 Operations Page
Operations Page
Dis-
play
Parameter name
Description
Range Default
Modbus
Relative Ad-
dress
CIP
Class
Instance
Attribute
hex (dec)
Probus
Index
Param-
eter ID
Data
Type
& Read/
Write
[``o;u]
[ o.v]
Process Value (1 to 2)
Output Value
View the value of this
function block's output.
-1,999.000 to 9,999.000°F
or units
-1,128.000 to 5,537.000°C
0.0 Instance 1
Map 1 Map 2
- - - - 3322
Instance 2
Map 1 Map 2
- - - - 3392
0x7E (126)
1 to 2
0x16 (22)
- - - - 26022 float
R
No
Dis-
play
Process Value (1 to 2)
Output Error
View reported cause for
Process output malfunc-
tion.
[none] None (61)
[open] Open (65)
[shrt] Shorted (127)
[`e;m] Measurement er-
ror (140)
[e;Cal] Bad calibration
data (139)
[er;ab] Ambient error (9)
[e;rtd] RTD error (14)
[fail] Fail (32)
[e;rm] Math error (1423)
[Nsrc] Not sourced (246)
[stal] Stale (1617)
[no;pr] Can't process
(1659)
None Instance 1
Map 1 Map 2
- - - - 3332
Instance 2
Map 1 Map 2
- - - - 3402
0x86 (134)
1 to 2
0x1B (27)
- - - - 26027 uint
R
[`dio]
[oPEr]
Digital Input/Output Menu
[`do;S]
[ do.S]
Digital Output (5 to 12)
Output State
View the state of this
output.
[`off] Off (62)
[``on] On (63)
Instance 5
Map 1 Map 2
1012 1132
Offset to next
instance equals
+30
0x6A (106)
5 to C (12)
7
90 6007 uint
R
[`di;S]
[ di.S]
Digital Input (5 to 12)
Input State
View this event input
state.
[`off] Off (62)
[``on] On (63)
- - - - Instance 5
Map 1 Map 2
1020 1140
Offset to next
instance equals
+30
0x6A (106)
5 to C (12)
0xB (11)
- - - - 6011 uint
R
[`ei;S]
[ Ei.S]
Digital Input (5 to 6)
Event Status
View this event input
state.
[`iact] Inactive (41)
[``act] Active (5)
Instance 5
Map 1 Map 2
1408 1648
Offset to next
instance equals
+20
0x6E (110)
5 to 6
5
140 10005 uint
R
[`ei;S]
[ Ei.S]
Digital Input (7 to 12)
Event Status
View this event input
state.
[`iact] Inactive (41)
[``act] Active (5)
Instance 7
Map 1 Map 2
1448 1688
Offset to next
instance equals
+20
0x6E (110)
7 to C (12)
5
140 10005 uint
R
No Dis-
play
EZ-Key/s (1 to 2)
Event Status
View this event input
state.
[`iact] Inactive (41)
[``act] Active (5)
Off Instance 1
Map 1 Map 2
1328 1568
Instance 2
Map 1 Map 2
1348 1588
0x6E (110)
3 to 4
5
140 10005 uint
R
Note:
Some values will be rounded off to fit in the four-character display. Full values can
be read with other interfaces.
R: Read
W: Write
E: EEPROM
S: User
Set