Owner manual

Watlow EZ-ZONE
®
PM Integrated Controller 64 Chapter 5 Operations Page
Operations Page
Dis-
play
Parameter name
Description
Range Default
Modbus
Relative Ad-
dress
CIP
Class
Instance
Attribute
hex (dec)
Probus
Index
Param-
eter ID
Data
Type
& Read/
Write
No
Dis-
play
Math (1)
Math Output Error
View reported cause for
math malfunction.
[none] None (61)
[open] Open (65)
[shrt] Shorted (127)
[`e;m] Measurement er-
ror (140)
[e;Cal] Bad calibration
data (139)
[er;ab] Ambient error (9)
[e;rtd] RTD error (14)
[fail] Fail (32)
[er;m] Math error (1423)
[nSrc] Not sourced (246)
[stal] Stale (1617)
[no;pr] Can't process
(1659)
- - - - Instance 1
Map 1 Map 2
- - - - 3056
0x7D
(125)
1
0x1D (29)
- - - - 25029 uint
R
[`SoF]
[oPEr]
Special Output Function Menu
[`Su;A]
[ Sv.A]
Special Output Func-
tion (1)
Source Value 1
View the value of Source
A which is connected to
Loop Power 1.
-1,999.000 to 9,999.000°F
or units
-1,128.000 to 5,537.000°C
- - - - Instance 1
Map 1 Map 2
- - - - 3852
0x87 (135)
1
7
- - - - 35007 float
R
[`Su;b]
[ Su.b]
Special Output Func-
tion (1)
Source Value 2
View the value of Source
B which is connected to
Loop Power 2.
-1,999.000 to 9,999.000°F
or units
-1,128.000 to 5,537.000°C
- - - - Instance 1
Map 1 Map 2
- - - - 3854
0x87 (135)
1
8
- - - - 35008 float
R
[`o;u1]
[ o.v1]
Special Output Func-
tion (1)
Output Value 1
View the value of this
function's Output 1.
-1,999.000 to 9,999.000°F
or units
-1,128.000 to 5,537.000°C
- - - - Instance 1
Map 1 Map 2
- - - - 3858
0x87 (135)
1
0xA (10)
- - - - 35010 float
R
[`o;u2]
[ o.v2]
Special Output Func-
tion (1)
Output Value 2
View the value of this
function's Output 2.
-1,999.000 to 9,999.000°F
or units
-1,128.000 to 5,537.000°C
- - - - Instance 1
Map 1 Map 2
- - - - 3862
0x87 (135)
1
0xC (12)
- - - - 35012 float
R
No
Dis-
play
Special Output Func-
tion (1)
Output Error 1
View reported cause for
output malfunction.
[none] None (61)
[open] Open (65)
[shrt] Shorted (127)
[`e;m] Measurement er-
ror (140)
[e;Cal] Bad calibration
data (139)
[er;ab] Ambient error (9)
[e;rtd] RTD error (14)
[fail] Fail (32)
[er;m] Math error (1423)
[nSrc] Not sourced (246)
[stal] Stale (1617)
[no;pr] Can't process
(1659)
- - - - Instance 1
Map 1 Map 2
- - - - 3860
0x87 (135)
1
0x0B (11)
- - - - 35011 uint
R
Note:
Some values will be rounded off to fit in the four-character display. Full values can
be read with other interfaces.
R: Read
W: Write
E: EEPROM
S: User
Set