Owner manual

Watlow EZ-ZONE
®
PM Integrated Controller 65 Chapter 5 Operations Page
Operations Page
Dis-
play
Parameter name
Description
Range Default
Modbus
Relative Ad-
dress
CIP
Class
Instance
Attribute
hex (dec)
Probus
Index
Param-
eter ID
Data
Type
& Read/
Write
No
Dis-
play
Special Output Func-
tion (1)
Output Error 2
View reported cause for
output malfunction.
[none] None (61)
[open] Open (65)
[shrt] Shorted (127)
[`e;m] Measurement er-
ror (140)
[e;Cal] Bad calibration
data (139)
[er;ab] Ambient error (9)
[e;rtd] RTD error (14)
[fail] Fail (32)
[er;m] Math error (1423)
[nSrc] Not sourced (246)
[stal] Stale (1617)
[no;pr] Can't process
(1659)
- - - - Instance 1
Map 1 Map 2
- - - - 3940
0x87 (135)
1
0x0D (13)
- - - - 35013 uint
R
[P;Sta]
[oPEr]
Profile Status Menu
Profile Menu appears if:
(PM _ [R, B*, N, E*] _ _ _-_ _ _ _ _ _ _)
* Available with PM8/9 only
* Some parameters in the Profile Status Menu can be changed for the
currently running profile, but should only be changed by knowledge-
able personnel and with caution. Changing parameters via the Pro-
file Status Menu will not change the stored profile but will have an
immediate impact on the profile that is running.
Changes made to profile parameters in the Profiling Pages will be
saved and will also have an immediate impact on the running profile.
[P;Str]
[P.Str]
Profile Status
Profile Start
Select step to act upon.
1 to 40 1 Instance 1
Map 1 Map 2
2520 4340
0x7A (122)
1
1
204 22001 uint
RW
[P;ACr]
[PACr]
Profile Status
Action Request
[nonE] None (61)
[step] Step Start (89)
[`End] Terminate (148)
[rESU] Resume (147)
[PAUS] Pause (146)
[ProF] Profile (77)
None Instance 1
Map 1 Map 2
2540 4360
0x7A (122)
1
0xB (11)
205 22011 uint
RW
[`StP]
[ StP]
Profile Status
Step
View the currently run-
ning step.
1 to 40 0 (none) Instance 1
Map 1 Map 2
2526 4346
0x7A (122)
1
4
- - - - 22004 uint
R
[S;typ]
[S.typ]
Profile Status
Active Step Type
View the currently run-
ning step type.
UStP] Unused Step (50)
[`End] End (27)
[``JL] Jump Loop (116)
[CloC] Wait For Time
(1543)
[W;bo] Wait For Both
(210)
[W;Pr] Wait For Process
(209)
[`W;E] Wait For Event
(144)
[SoAH] Soak (87)
[``ti] Time (143)
[rAtE] Rate (81)
Instance 1
Map 1 Map 2
2544 4364
0x7A (122)
1
0xD (13)
- - - - 22013 uint
R
[t;SP1]
[tg.SP]
Profile Status
*Target Set Point
Loop 1
View or change the tar-
get set point of the cur-
rent step.
-1,999.000 to 9,999.000°F
or units
-1,128.000 to 5,537.000°C
0.0°F
or
units
-18.0°C
Instance 1
Map 1 Map 2
2542 4362
0x7A (122)
1
0xC (12)
- - - - 22012 float
RW
Note:
Some values will be rounded off to fit in the four-character display. Full values can
be read with other interfaces.
R: Read
W: Write
E: EEPROM
S: User
Set