Owner manual

Watlow EZ-ZONE
®
PM Integrated Controller 70 Chapter 6 Setup Page
Setup Page
Dis-
play
Parameter Name
Description
Range Default
Modbus Rela-
tive
Address
CIP
Class
Instance
Attribute
hex (dec)
Pro-
fibus
Index
Param-
eter ID
Data
Type
&
Read/
Write
[`r;hi]
[ r.hi]
Analog Input (1 to 2)
Range High
Set the high range for
this function block's
output.
-1,999.000 to 9,999.000 9,999 Instance 1
Map 1 Map 2
394 394
Instance 2
Map 1 Map 2
474 484
0x68 (104)
1 to 2
0x12 (18)
9 4018 float
RWES
[`P;EE]
[ P.EE]
Analog Input (1 to 2)
Process Error Enable
Turn the Process Error
Low feature on or off.
[`off] Off (62)
[Low] Low (53)
Off Instance 1
Map 1 Map 2
418 418
Instance 2
Map 1 Map 2
498 508
0x68 (104)
1 to 2
0x1E (30)
10 4030 uint
RWES
[`P;EL]
[ P.EL]
Analog Input (1 to 2)
Process Error Low
Value
If the process value drops
below this value, it will
trigger an input error.
-100.0 to 1,000.0 0.0 Instance 1
Map 1 Map 2
420 420
Instance 2
Map 1 Map 2
500 510
0x68 (104)
1 to 2
0x1F (31)
11 4031 float
RWES
[``t;C]
[ t.C]
Analog Input (1 to 2)
Thermistor Curve
Select a curve to apply to
the thermistor input.
[```A] Curve A (1451)
[```b] Curve B (1452)
[```C] Curve C (1453)
[CUSt] Custom (180)
Curve A Instance 1
Map 1 Map 2
434 434
Instance 2
Map 1 Map 2
514 524
0x68 (104)
1 to 2
20x6 (38)
- - - - 4038 uint
RWES
[``r;r]
[ r.r]
Analog Input (1 to 2)
Resistance Range
Set the maximum resis-
tance of the thermistor
input.
[```5] 5K (1448)
[``10] 10K (1360)
[``20] 20K (1361)
[``40] 40K (1449)
40K Instance 1
Map 1 Map 2
432 432
Instance 2
Map 1 Map 2
512 522
0x68 (104)
1 to 2
0x25 (37)
- - - - 4037 uint
RWES
[`FiL]
[ FiL]
Analog Input (1 to 2)
Filter
Filtering smooths out the
process signal to both the
display and the input.
Increase the time to in-
crease filtering.
0.0 to 60.0 seconds 0.5 Instance 1
Map 1 Map 2
386 386
Instance 2
Map 1 Map 2
466 476
0x68 (104)
1 to 2
0xE (14)
12 4014 float
RWES
[`i;Er]
[ i.Er]
Analog Input (1 to 2)
Input Error Latching
Turn input error latching
on or off. If latching is on,
errors must be manually
cleared.
[`off] Off (62)
[``on] On (63)
Off Instance 1
Map 1 Map 2
414 414
Instance 2
Map 1 Map 2
494 504
0x68 (104)
1 to 2
0x1C (28)
- - - - 4028 uint
RWES
[`dEC]
[ dEC]
Analog Input (1 to 2)
Display Precision
Set the precision of the
displayed value.
[```0] Whole (105)
[``0;0] Tenths (94)
[`0;00] Hundredths (40)
[0;000] Thousandths (96)
Whole Instance 1
Map 1 Map 2
398 398
Instance 2
Map 1 Map 2
478 488
0x68 (104)
1 to 2
0x14 (20)
- - - - 4020 uint
RWES
Note:
Some values will be rounded off to fit in the four-character display. Full values can be read
with other interfaces.
R: Read
W: Write
E: EEPROM
S: User
Set