Owner manual

Watlow EZ-ZONE
®
PM Integrated Controller 71 Chapter 6 Setup Page
Setup Page
Dis-
play
Parameter Name
Description
Range Default
Modbus Rela-
tive
Address
CIP
Class
Instance
Attribute
hex (dec)
Pro-
fibus
Index
Param-
eter ID
Data
Type
&
Read/
Write
[`i;Ca]
[ i.CA]
Analog Input (1 to 2)
Calibration Offset
Offset the input reading
to compensate for lead
wire resistance or other
factors that cause the in-
put reading to vary from
the actual process value.
-1,999.000 to 9,999.000°F or
units
-1,110.555 to 5,555.000°C
0.0 Instance 1
Map 1 Map 2
382 382
Instance 2
Map 1 Map 2
462 472
0x68 (104)
1 to 2
0x0C (12)
2 4012 float
RWES
[`Ain]
[ Ain]
Analog Input (1 to 2)
Analog Input Value
View the process value.
Note:
Ensure that the Input
Error Status (below)
indicates no error (61)
when reading this
value using a field bus
protocol. If an error
exists, the last known
value prior to the er-
ror occurring will be
returned.
-1,999.000 to 9,999.000°F or
units
-1,128.000 to 5,537.000°C
- - - - Instance 1
Map 1 Map 2
360 360
Instance 2
Map 1 Map 2
440 450
0x68 (104)
1 to 2
1
0 4001 float
R
[`i;Er]
[ i.Er]
Analog Input (1 to 2)
Input Error Status
View the cause of the
most recent error. If
the
[Attn]
message is
[Er;i1]
or
[Er;i2]
, this
parameter will display
the cause of the input
error.
[nonE] None (61)
[OPEn] Open (65)
[Shrt] Shorted (127)
[`E;M] Measurement Error
(149)
[E;CAL] Bad Calibration Data
(139)
[Er;Ab] Ambient Error (9)
[E;;Rtd] RTD Error (141)
[FAiL] Fail (32)
[Nsrc] Not Sourced (246)
None Instance 1
Map 1 Map 2
362 362
Instance 2
Map 1 Map 2
442 452
0x68 (104)
1 to 2
2
1 4002 float
R
[`Lnr]
[`Set]
Linearization Menu
[``Fn]
[ Fn]
Linearization (1 to 2)
Function
Set how this function
will linearize Source A
which is Analog Input 1.
Source A of Linearization
2 is Analog Input 2.
[`oFF] Off (62)
[intr] Interpolated (1482)
Off Instance 1
Map 1 Map 2
- - - - 3568
Instance 2
Map 1 Map 2
- - - - 3638
0x86 (134)
1 to 2
5
155 34005 uint
RWES
[Unit]
[Unit]
Linearization (1 to 2)
Units
Set the units of Source A
or Analog Input 1. Source
A of Linearization 2 is
Analog Input 2.
[`Src] Source (1539)
[``rh] Relative Humidty
(1538)
[`pro] Process (75)
[PWr] Power (73)
[`r;tp] Relative Temperature
(1541)
[`A;tP] Absolute Temperature
(1540)
[nonE] None (61)
Source Instance 1
Map 1 Map 2
- - - - 3616
Instance 2
Map 1 Map 2
- - - - 3686
0x86 (134)
1 to 2
0x29 (41)
156 34029 uint
RWES
Note:
Some values will be rounded off to fit in the four-character display. Full values can be read
with other interfaces.
R: Read
W: Write
E: EEPROM
S: User
Set