Owner manual

Watlow EZ-ZONE
®
PM Integrated Controller 73 Chapter 6 Setup Page
Setup Page
Dis-
play
Parameter Name
Description
Range Default
Modbus Rela-
tive
Address
CIP
Class
Instance
Attribute
hex (dec)
Pro-
fibus
Index
Param-
eter ID
Data
Type
&
Read/
Write
[`oP;5]
[ op.5]
Linearization (1 to 2)
Output Point 5
Set the value that will be
mapped to input 5.
-1,999.000 to 9,999.000 4.0 Instance 1
Map 1 Map 2
- - - - 3602
Instance 2
Map 1 Map 2
- - - - 3672
0x86 (134)
1 to 2
0x16 (22)
166 34022 float
RWES
[`iP;6]
[ ip.6]
Linearization (1 to 2)
Input Point 6
Set the value that will be
mapped to output 6.
-1,999.000 to 9,999.000 5.0 Instance 1
Map 1 Map 2
- - - - 3584
Instance 2
Map 1 Map 2
- - - - 3654
0x86 (134)
1 to 2
0xD (13)
167 34013 float
RWES
[`oP;6]
[ op.6]
Linearization (1 to 2)
Output Point 6
Set the value that will be
mapped to input 6.
-1,999.000 to 9,999.000 5.0 Instance 1
Map 1 Map 2
- - - - 3604
Instance 2
Map 1 Map 2
- - - - 3674
0x86 (134)
1 to 2
0x17 (23)
168 34023 float
RWES
[`iP;7]
[ ip.7]
Linearization (1 to 2)
Input Point 7
Set the value that will be
mapped to output 7.
-1,999.000 to 9,999.000 6.0 Instance 1
Map 1 Map 2
- - - - 3586
Instance 2
Map 1 Map 2
- - - - 3656
0x86 (134)
1 to 2
0xE (14)
169 34014 float
RWES
[`oP;7]
[ op.7]
Linearization (1 to 2)
Output Point 7
Set the value that will be
mapped to input 7.
-1,999.000 to 9,999.000 6.0 Instance 1
Map 1 Map 2
- - - - 3606
Instance 2
Map 1 Map 2
- - - - 3676
0x86 (134)
1 to 2
0x18 (24)
170 34024 float
RWES
[`iP;8]
[ ip.8]
Linearization (1 to 2)
Input Point 8
Set the value that will be
mapped to output 8.
-1,999.000 to 9,999.000 7.0 Instance 1
Map 1 Map 2
- - - - 3588
Instance 2
Map 1 Map 2
- - - - 3658
0x86 (134)
1 to 2
0xF (15)
171 34015 float
RWES
[`oP;8]
[ op.8]
Linearization (1 to 2)
Output Point 8
Set the value that will be
mapped to input 8.
-1,999.000 to 9,999.000 7.0 Instance 1
Map 1 Map 2
- - - - 3608
Instance 2
Map 1 Map 2
- - - - 3678
0x86 (134)
1 to 2
0x19 (25)
172 34025 float
RWES
[`iP;9]
[ ip.9]
Linearization (1 to 2)
Input Point 9
Set the value that will be
mapped to output 9.
-1,999.000 to 9,999.000 8.0 Instance 1
Map 1 Map 2
- - - - 3590
Instance 2
Map 1 Map 2
- - - - 3660
0x86 (134)
1 to 2
0x10 (16)
173 34016 float
RWES
[`oP;9]
[ op.9]
Linearization (1 to 2)
Output Point 9
Set the value that will be
mapped to input 9.
-1,999.000 to 9,999.000 8.0 Instance 1
Map 1 Map 2
- - - - 3610
Instance 2
Map 1 Map 2
- - - - 3680
0x86 (134)
1 to 2
0x1A (26)
174 34026 float
RWES
Note:
Some values will be rounded off to fit in the four-character display. Full values can be read
with other interfaces.
R: Read
W: Write
E: EEPROM
S: User
Set