PM Integrated Controller 81 Chapter 6 Setup Page
Setup Page
Dis-
play
Parameter Name
Description
Range Default
Modbus Rela-
tive
Address
CIP
Class
Instance
Attribute
hex (dec)
Pro-
fibus
Index
Param-
eter ID
Data
Type
&
Read/
Write
[`C;Pb]
[ C.Pb]
Control Loop (1 to 2)
Cool Proportional
Band
Set the PID propor-
tional band for the cool
outputs.
0.001 to 9,999.000°F or units
0.001 to 5,555.000°C
25.0°F or
units
14.0°C
Instance 1
Map 1 Map 2
1892 2372
Instance 2
Map 1 Map 2
1962 2442
0x97
(151)
1 to 2
7
67 8012 float
RWES
[`C;hy]
[ C.hy]
Control Loop (1 to 2)
Cool Hysteresis
Set the control switch-
ing hysteresis for on-off
control. This determines
how far into the “on”
region the process value
needs to move before
the output turns on.
0.001 to 9,999.000°F or units
0.001 to 5,555.000°C
3.0°F or
units
2.0°C
Instance 1
Map 1 Map 2
1902 2382
Instance 2
Map 1 Map 2
1972 2522
0x97
(151)
1 to 2
0xC (12)
68 8013 float
RWES
[``ti]
[ ti]
Control Loop (1 to 2)
Time Integral
Set the PID integral for
the outputs.
0 to 9,999 seconds per repeat
180 sec-
onds per
repeat
Instance 1
Map 1 Map 2
1894 2374
Instance 2
Map 1 Map 2
1964 2444
0x97
(151)
1 to 2
8
69 8006 float
RWES
[``td]
[ td]
Control Loop (1 to 2)
Time Derivative
Set the PID derivative
time for the outputs.
0 to 9,999 seconds 0
seconds
Instance 1
Map 1 Map 2
1896 2376
Instance 2
Map 1 Map 2
1966 2446
0x97
(151)
1 to 2
9
70 8007 float
RWES
[``dB]
[ db]
Control Loop (1 to 2)
Dead Band
Set the offset to the
proportional band.
With a negative value,
both heating and cool-
ing outputs are active
when the process value
is near the set point.
A positive value keeps
heating and cooling out-
puts from fighting each
other.
-1,000.0 to 1,000.0°F or units
-556 to 556°C
0 Instance 1
Map 1 Map 2
1898 2378
Instance 2
Map 1 Map 2
1968 2448
0x97
(151)
1 to 2
0xA (10)
71 8008 float
RWES
[t;tUn]
[t.tUn]
Control Loop (1 to 2)
TRU-TUNE+™ Enable
Enable or disable the
TRU-TUNE+™ adap-
tive tuning feature.
[``no] No (59)
[`YES} Yes (106)
No
Instance 1
Map 1 Map 2
1910 2390
Instance 2
Map 1 Map 2
1980 2460
0x97 (151)
1 to 2
0x10 (16)
- - - - 8022 uint
RWES
Note:
Some values will be rounded off to fit in the four-character display. Full values can be read
with other interfaces.
R: Read
W: Write
E: EEPROM
S: User
Set