PM Integrated Controller 82 Chapter 6 Setup Page
Setup Page
Dis-
play
Parameter Name
Description
Range Default
Modbus Rela-
tive
Address
CIP
Class
Instance
Attribute
hex (dec)
Pro-
fibus
Index
Param-
eter ID
Data
Type
&
Read/
Write
[t;bnd]
[t.bnd]
Control Loop (1 to 2)
TRU-TUNE+™ Band
Set the range, centered
on the set point, within
which TRU-TUNE+™
will be in effect. Use this
function only if the con-
troller is unable to adap-
tive tune automatically.
0 to 100 0 Instance 1
Map 1 Map 2
1912 2392
Instance 2
Map 1 Map 2
1982 2462
0x97 (151)
1 to 2
0x11 (17)
- - - - 8034 uint
RWES
[`t;gn]
[ t.gn]
Control Loop (1 to 2)
TRU-TUNE+™ Gain
Select the responsiveness
of the TRU-TUNE+™
adaptive tuning calcula-
tions. More responsive-
ness may increase over-
shoot.
1 to 6 3 Instance 1
Map 1 Map 2
1914 2394
Instance 2
Map 1 Map 2
1984 2464
0x97 (151)
1 to 2
0x12 (18)
- - - - 8035 uint
RWES
[A;tSP]
[A.tSP}
Control Loop (1 to 2)
Autotune Set Point
Set the set point that
the autotune will use, as
a percentage of the cur-
rent set point.
50.0 to 200.0% 90.0 Instance 1
Map 1 Map
2
1918 2398
Instance 2
Map 1 Map
2
1988 2468
0x97
(151)
1 to 2
0x14 (20)
- - - - 8025 float
RWES
[t;Agr]
[t.Agr]
Control Loop (1 to 2)
Autotune Aggressive-
ness
Select the aggressiveness
of the autotuning calcu-
lations.
[Undr] Under damped (99)
[Crit] Critical damped (21)
[OuEr] Over damped (69)
Critical Instance 1
Map 1 Map 2
1916 2396
Instance 2
Map 1 Map 2
1986 2466
0x97 (151)
1 to 2
0x13 (19)
- - - - 8024 uint
RWES
[`p;dl]
[ P.dL]
Control Loop (1 to 2)
Peltier Delay
Set a value that will
cause a delay when
switching from heat
mode to cool mode.
0.0 to 5.0 seconds 0.0 Instance 1
Map 1 Map 2
1934 2414
Instance 2
Map 1 Map 2
2004 2484
0x97 (151)
1 to 2
0x1C (28)
- - - - 8051 float
RWES
[`r;En]
[ r.En]
Control Loop (1 to 2)
Remote Enable
Enable this loop to
switch control to the
remote set point.
[``no] No (59)
[`YES] Yes (106)
No Instance 1
Map 1 Map 2
2200 2680
Instance 2
Map 1 Map 2
2280 2760
0x6B
(107)
1 to 2
0x15 (21)
48 7021 uint
RWES
[`r;ty]
[ r.ty]
Control Loop (1 to 2)
Remote Set Point Type
Set what type of set
point will be used.
[AUto] Auto (10)
[MAn] Manual (54)
Auto Instance 1
Map 1 Map 2
2202 2682
Instance 2
Map 1 Map 2
2282 2762
0x6B (107)
1 to 2
0x16 (22)
- - - - 7022 uint
RWES
Note:
Some values will be rounded off to fit in the four-character display. Full values can be read
with other interfaces.
R: Read
W: Write
E: EEPROM
S: User
Set