Owner manual

Watlow EZ-ZONE
®
PM Integrated Controller 83 Chapter 6 Setup Page
Setup Page
Dis-
play
Parameter Name
Description
Range Default
Modbus Rela-
tive
Address
CIP
Class
Instance
Attribute
hex (dec)
Pro-
fibus
Index
Param-
eter ID
Data
Type
&
Read/
Write
[`UFA]
[UFA]
Control Loop (1 to 2)
User Failure Action
Select what the control-
ler outputs will do when
the user switches control
to manual mode.
[`oFF] Off, sets output power
to 0% (62)
[bPLS] Bumpless Transfer,
maintains same output
power, if it was less than 75%
and stable, otherwise 0% (14)
[MAn] Fixed Power, sets out-
put power to Manual Power
setting (33)
[USEr] User, sets output pow-
er to last open-loop set point
the user entered (100)
User Instance 1
Map 1 Map 2
2182 2662
Instance 2
Map 1 Map 2
2262 2742
0x6B (107)
1 to 2
0xC (12)
- - - - 7012 uint
RWES
[FAiL]
[FAiL]
Control Loop (1 to 2)
Input Error Failure
Select what the control-
ler outputs will do when
an input error switches
control to manual mode.
[`oFF] Off, sets output power
to 0% (62)
[bPLS] Bumpless Transfer,
maintains same output
power, if it was less than 75%
and stable, otherwise 0% (14)
[MAn] Fixed Power, sets out-
put power to Fixed Power
setting (33)
[USEr] User, sets output pow-
er to last open-loop set point
the user entered (100)
User Instance 1
Map 1 Map 2
2184 2664
Instance 2
Map 1 Map 2
2264 2744
0x6B (107)
1 to 2
0xD (13)
- - - - 7013 uint
RWES
[MAn]
[MAn]
Control Loop (1 to 2)
Fixed Power
Set the manual output
power level that will take
effect if an input error
failure occurs while User
Failure Action is set to
Manual Fixed.
Set Point Open Loop Limit
Low to Set Point Open Loop
Limit High (Setup Page)
0.0 Instance 1
Map 1 Map 2
2180 2660
Instance 2
Map 1 Map 2
2260 2740
0x6B (107)
1 to 2
0xB (11)
- - - - 7011 float
RWES
[`L;dE]
[ L.dE]
Control Loop (1 to 2)
Open Loop Detect En-
able
Turn on the open-loop
detect feature to monitor
a closed-loop operation
for the appropriate re-
sponse.
[``no] No (59)
[`YES} Yes (106)
No Instance 1
Map 1 Map 2
1922 2402
Instance 2
Map 1 Map 2
1992 2472
0x97 (151)
1 to 2
0x16 (22)
74 8039 uint
RWES
[`L;dt]
[ L.dt]
Control Loop (1 to 2)
Open Loop Detect
Time
The Open Loop Detect
Deviation value must oc-
cur for this time period
to trigger an open-loop
error.
0 to 3,600 seconds 240 Instance 1
Map 1 Map 2
1924 2404
Instance 2
Map 1 Map 2
1994 2474
0x97 (151)
1 to 2
0x17 (23)
75 8040 uint
RWES
[`L;dd]
[ L.dd]
Control Loop (1 to 2)
Open Loop Detect De-
viation
The value entered repre-
sents the Process Value
deviation that must
occur to trigger an open-
loop error.
-1,999.000 to 9,999.000°F or
units
-1,110.555 to 5,555.000°C
10.0°F or
units
6.0°C
Instance 1
Map 1 Map 2
1926 2406
Instance 2
Map 1 Map 2
1996 2476
0x97 (151)
1 to 2
0x18 (24)
76 8041 float
RWES
Note:
Some values will be rounded off to fit in the four-character display. Full values can be read
with other interfaces.
R: Read
W: Write
E: EEPROM
S: User
Set