Owner manual

Watlow EZ-ZONE
®
PM Integrated Controller 86 Chapter 6 Setup Page
Setup Page
Dis-
play
Parameter Name
Description
Range Default
Modbus Rela-
tive
Address
CIP
Class
Instance
Attribute
hex (dec)
Pro-
fibus
Index
Param-
eter ID
Data
Type
&
Read/
Write
[`o;Ct]
[ o.Ct]
Output Digital (1 to 4)
Output Control
Set the output control
type. This parameter
is only used with PID
control, but can be set
anytime.
[`Ftb] Fixed Time Base (34)
[`utb] Variable Time Base
(103)
Fixed
Time
Base
Instance 1
Map 1 Map 2
882 1002
Offset to next
instance (Map
1 & Map 2)
equals +30
0x6A (106)
1 to 4
2
85 6002 uint
RWES
[`o;tb]
[ o.tb]
Output Digital (1 to 4)
Output Time Base
Set the time base for
fixed-time-base control.
0.1 to 60.0 seconds (solid-state
relay or switched dc)
5.0 to 60.0 seconds (mechani-
cal relay or NO-ARC power
control)
1.0 sec.
for SSR
or swdc
5.0 for
relay
Instance 1
Map 1 Map 2
884 1004
Offset to next
instance (Map
1 & Map 2)
equals +30
0x6A (106)
1 to 4
3
86 6003 float
RWES
[`o;Lo]
[ o.Lo]
Output Digital (1 to 4)
Output Low Power
Scale
The power output will
never be less than the
value specified and will
represent the value at
which output scaling
begins.
0.0 to 100.0% 0.0% Instance 1
Map 1 Map 2
896 1016
Offset to next
instance (Map
1 & Map 2)
equals +30
0x6A (106)
1 to 4
9
87 6009 float
RWES
[`o;hi]
[ o.hi]
Output Digital (1 to 4)
Output High Power
Scale
The power output will
never be greater than
the value specified and
will represent the value
at which output scaling
stops.
0.0 to 100.0% 100.0% Instance 1
Map 1 Map 2
898 1018
Offset to next
instance (Map
1 & Map 2)
equals +30
0x6A (106)
1 to 4
0xA (10)
88 6010 float
RWES
[`o;ty]
[ o.ty]
Output Process (1 or 3)
Output Type
Select whether the pro-
cess output will operate
in volts or milliamps.
[uoLt] Volts (104)
[`MA] Milliamps (112)
Volts Instance 1
Map 1 Map 2
720 840
Instance 3
Map 1 Map 2
800 920
0x76 (118)
1 or 3
1
95 18001 uint
RWES
[``Fn]
[ Fn]
Output Process (1 or 3)
Output Function
Set the type of func-
tion that will drive this
output.
[`oFF] Off (62)
[heat] Heat (36)
[Cool] Cool (20)
[dupl] Duplex (212)
[ALM] Alarm (6)
[Ent;A] Profile Event Out A
(233)
[Ent;b] Profile Event Out B
(234)
[rmt] Retransmit (213)
Off Instance 1
Map 1 Map 2
722 842
Instance 3
Map 1 Map 2
802 922
0x76 (118)
1 or 3
2
96 18002 uint
RWES
Note:
Some values will be rounded off to fit in the four-character display. Full values can be read
with other interfaces.
R: Read
W: Write
E: EEPROM
S: User
Set