Owner manual

Watlow EZ-ZONE
®
PM Integrated Controller 87 Chapter 6 Setup Page
Setup Page
Dis-
play
Parameter Name
Description
Range Default
Modbus Rela-
tive
Address
CIP
Class
Instance
Attribute
hex (dec)
Pro-
fibus
Index
Param-
eter ID
Data
Type
&
Read/
Write
[`r;Sr]
[ r.Sr]
Output Process (1 or 3)
Retransmit Source
Select the value that will
be retransmitted.
[``Ai] Analog Input (142)
[StPt] Set Point (85)
[CUrr] Current (22)
[``Pu] Process Value (241)
Analog
Input
Instance 1
Map 1 Map 2
724 844
Instance 3
Map 1 Map 2
804 924
0x76 (118)
1 or 3
3
97 18003 uint
RWES
[``Fi]
[ Fi]
Output Process (1 or 3)
Output Function In-
stance
Set the instance of the
function selected above.
1 to 4 1 Instance 1
Map 1 Map 2
726 846
Instance 3
Map 1 Map 2
806 926
0x76 (118)
1 or 3
4
98 18004 uint
RWES
[`S;Lo]
[ S.Lo]
Output Process (1 or 3)
Scale Low
Set the scale low for pro-
cess output in electrical
units. This value; in volts
or milliamps, will cor-
respond to 0% PID power
output or range low re-
transmit output.
-100.0 to 100.0 0.00 Instance 1
Map 1 Map 2
736 856
Instance 3
Map 1 Map 2
816 936
0x76 (118)
1 or 3
9
99 18009 float
RWES
[`S;hi]
[ S.hi]
Output Process (1 or 3)
Scale High
Set the scale high for
process output in
electrical units. This
value; in volts or
milliamps, will corre-
spond to 100% PID
power output or range
high retransmit output.
-100.0 to 100.0 10.00 Instance 1
Map 1 Map 2
738 858
Instance 3
Map 1 Map 2
818 938
0x76 (118)
1 or 3
0xA (10)
100 18010 float
RWES
[`r;Lo]
[ r.Lo]
Output Process (1 or 3)
Range Low
Set the minimum value
of the retransmit value
range in process units.
When the retransmit
source is at this value,
the retransmit output
will be at its Scale Low
value.
-1,999.000 to 9,999.000°F or
units
-1,128.000 to 5,537.000°C
0.0°F or
units
-18°C
Instance 1
Map 1 Map 2
740 860
Instance 3
Map 1 Map 2
820 940
0x76 (118)
1 or 3
0xB (11)
101 18011 float
RWES
[`r;hi]
[ r.hi]
Output Process (1 or 3)
Range High
Set the maximum value
of the retransmit value
range in process units.
When the retransmit
source is at this value,
the retransmit output
will be at its Scale High
value.
-1,999.000 to 9,999.000°F or
units
-1,128.000 to 5,537.000°C
100.0°F or
units
38.0°C
Instance 1
Map 1 Map 2
742 862
Instance 3
Map 1 Map 2
822 942
0x76 (118)
1 or 3
0xC (12)
102 18012 float
RWES
Note:
Some values will be rounded off to fit in the four-character display. Full values can be read
with other interfaces.
R: Read
W: Write
E: EEPROM
S: User
Set