Owner manual

Watlow EZ-ZONE
®
PM Integrated Controller 89 Chapter 6 Setup Page
Setup Page
Dis-
play
Parameter Name
Description
Range Default
Modbus Rela-
tive
Address
CIP
Class
Instance
Attribute
hex (dec)
Pro-
fibus
Index
Param-
eter ID
Data
Type
&
Read/
Write
[loop]
[LooP]
Alarm (1 to 4)
Control Loop
Set the instance of the
Set Point Closed, Control
Loop, that will be refer-
enced by the deviation
alarm.
Note:
Not available on single
loop models.
1 to 2 1 Instance 1
Map 1 Map 2
1524 1924
Offset to next
instance (Map
1 +50, Map 2
+60)
0x6D (109)
1 to 2
0x17 (23)
23 9023 uint
RWES
[`A;hy]
[ A.hy]
Alarm (1 to 4)
Alarm Hysteresis
Set the hysteresis for an
alarm. This determines
how far into the safe
region the process value
needs to move before the
alarm can be cleared.
0.001 to 9,999.000°F or units
0.001 to 5,555.000°C
1.0°F or
units
1.0°C
Instance 1
Map 1 Map 2
1484 1884
Offset to next
instance (Map
1 equals +50,
Map 2 +60)
0x6D (109)
1 to 4
3
24 9003 float
RWES
[`A;Lg]
[ A.Lg]
Alarm (1 to 4)
Alarm Logic
Select what the output
condition will be during
the alarm state.
[`AL;C] Close On Alarm (17)
[`AL;o] Open On Alarm (66)
Close On
Alarm
Instance 1
Map 1 Map 2
1488 1888
Offset to next
instance (Map
1 +50, Map 2
+60)
0x6D (109)
1 to 4
5
25 9005 uint
RWES
[`A;Sd]
[ A.Sd]
Alarm (1 to 4)
Alarm Sides
Select which side or sides
will trigger this alarm.
[both] Both (13)
[high] High (37)
[LoW] Low (53)
Both Instance 1
Map 1 Map 2
1486 1886
Offset to next
instance (Map
1 +50, Map 2
+60)
0x6D (109)
1 to 4
4
26 9004 uint
RWES
[`A;Lo]
[ A.Lo]
Alarm (1 to 4)
Alarm Low Set Point
If Alarm Type (Setup
Page, Alarm Menu) is
set to:
process - set the process
value that will trigger
a low alarm.
deviation - set the span
of units from the closed
loop set point that will
trigger a low alarm. A
negative set point rep-
resents a value below
closed loop set point. A
positive set point rep-
resents a value above
closed loop set point.
-1,999.000 to 9,999.000°F or
units
-1,128.000 to 5,537.000°C
32.0°F
or units
0.0°C
Instance 1
Map 1 Map 2
1482 1882
Offset to next
instance (Map
1 +50, Map 2
+60)
0x6D
(109)
1 to 4
2
18 9002 float
RWES
Note:
Some values will be rounded off to fit in the four-character display. Full values can be read
with other interfaces.
R: Read
W: Write
E: EEPROM
S: User
Set