Owner manual

Watlow EZ-ZONE
®
PM Integrated Controller 91 Chapter 6 Setup Page
Setup Page
Dis-
play
Parameter Name
Description
Range Default
Modbus Rela-
tive
Address
CIP
Class
Instance
Attribute
hex (dec)
Pro-
fibus
Index
Param-
eter ID
Data
Type
&
Read/
Write
[a;Clr]
[A.Clr]
Alarm (1 to 4)
Alarm Clear Request
Write to this register to
clear an alarm
Note:
If an alarm is setup
to latch when active
[a;Clr] will appear on
the display.
[`Clr] Clear (0)
[ignr] Ignore (204)
- - - - Instance 1
Map 1 Map 2
1504 1904
Offset to
next instance
(Map1 1
equals +50,
Map 2 equals
+60)
0x6D
(109)
1 to 4
0xD (13)
- - - - 9013 uint
W
[a;sir]
[A.Sir]
Alarm (1 to 4)
Alarm Silence Re-
quest
Write to this register to
silence an alarm
Note:
If an alarm is setup
to silence alarm when
active [a;sir] will ap-
pear on the display.
[`sil] Silence (1010)
- - - - Instance 1
Map 1 Map 2
1506 1906
Offset to
next instance
(Map1 1
equals +50,
Map 2 equals
+60)
0x6D
(109)
1 to 4
0xE (14)
- - - - 9014 uint
W
[`a;st]
[ A.St]
Alarm (1 to 4)
Alarm State
Current state of alarm
[`str] Startup (88)
[none] None (61)
[`blo] Blocked (12)
[`al;l] Alarm low (8)
[`al;h] Alarm high (7)
[`al;e] Error (28)
- - - - Instance 1
Map 1 Map 2
1496 1896
Offset to
next instance
(Map1 1
equals +50,
Map 2 equals
+60)
0x6D
(109)
1 to 4
9
- - - - 9009 uint
R
[CUrr]
[`Set]
Current Menu
[`C;Sd]
[ C.Sd]
Current (1)
Current Sides
Select which side or sides
will be monitored.
[`oFF] Off (62)
[high] High (37)
[low] Low (53)
[both] Both (13)
off Instance 1
Map 1 Map 2
1128 1368
0x73 (115)
1
5
145 15005 uint
RWES
[`C;Ur]
[ C.Ur]
Current (1)
Current Read Enable
Display under/over-range
current.
[``no] No (59)
[`yes] Yes (106)
no Instance 1
Map 1 Map 2
1126 1366
0x73 (115)
1
4
146 15004 uint
RWES
[`C;dt]
[ C.dt]
Current (1)
Input Current Detec-
tion Threshold
For factory adjustment
only.
3 to 59 9 Instance 1
Map 1 Map 2
1142 1382
0x73 (115)
1
0xC (12)
147 15012 uint
RWES
[`C;SC]
[ C.SC]
Current (1)
Current Scaling
Adjust scaling to match
the transformer's high
range.
0 to 9,999.000 50.0 Instance 1
Map 1 Map 2
1162 1402
0x73 (115)
1
0x16 (22)
148 15022 float
RWES
Note:
Some values will be rounded off to fit in the four-character display. Full values can be read
with other interfaces.
R: Read
W: Write
E: EEPROM
S: User
Set