PM Integrated Controller 92 Chapter 6 Setup Page
Setup Page
Dis-
play
Parameter Name
Description
Range Default
Modbus Rela-
tive
Address
CIP
Class
Instance
Attribute
hex (dec)
Pro-
fibus
Index
Param-
eter ID
Data
Type
&
Read/
Write
[C;;oFs]
[C.oFS]
Current (1)
Heater Current Offset
Calibrate the current
reading with an offset
value.
-9,999.000 to 9,999.000 0.0 Instance 1
Map 1 Map 2
1140 1380
0x73 (115)
1
0xB (11)
149 15011 float
RWES
[`C;;Si]
[ C.Si]
Current (1)
Current Output Source
Instance
Select which output in-
stance the current trans-
former will monitor.
1 to 12 1 Instance 1
Map 1 Map 2
1156 1396
0x73 (115)
1
0x13 (19)
150 15019 uint
RWES
[MAt]
[`Set]
Math Menu
[``Fn]
[ Fn]
Math (1)
Function
Set the operator that will
be applied to the sources.
[`oFF] Off (62)
[`P;SC] Process Scale (1371)
[`d;SC] Deviation Scale (1372)
Off Instance 1
Map 1 Map 2
- - - - 3040
0x7D (125)
1
0x15 (21)
128 25021 uint
RWES
[SFn;e]
[SFn.E]
Math (1)
Source Function E
Set the type of function
that will be used for this
source.
[nonE] None (61)
[`fUn] Function Key (1001)
[`dio] Digital I/O (1142)
None Instance 1
Map 1 Map 2
- - - - 3008
0x7D (125)
1
5
- - - - 25005 uint
RWES
[`si;e]
[ Si.E]
Math (1)
Source Instance E
Set the instance of the
function selected above.
1 to 12 1 Instance 1
Map 1 Map 2
- - - - 3018
0x7D (125)
1
0xA (10)
25010 float
RWES
[`S;Lo]
[ S.Lo]
Math (1)
Scale Low
This value will corre-
spond to Output Range
Low.
-1,999.000 to 9,999.000 0.0 Instance 1
Map 1 Map 2
- - - - 3046
0x7D (125)
1
0x18 (24)
129 25024 float
RWES
[`S;hi]
[ S.hi]
Math (1)
Scale High
This value will corre-
spond to Output Range
High.
-1,999.000 to 9,999.000 1.0 Instance 1
Map 1 Map 2
- - - - 3048
0x7D (125)
1
0x19 (25)
130 25025 float
RWES
[`r;Lo]
[ r.Lo]
Math (1)
Range Low
This value will corre-
spond to Input Scale Low.
-1,999.000 to 9,999.000 0.0 Instance 1
Map 1 Map 2
- - - - 3050
0x7D (125)
1
0x1A (26)
131 25026 float
RWES
[`r;hi]
[ r.hi]
Math (1)
Range High
This value will cor-
respond to Input Scale
High.
-1,999.000 to 9,999.000 1.0 Instance 1
Map 1 Map 2
- - - - 3052
0x7D (125)
1
0x1B (27)
132 25027 float
RWES
Note:
Some values will be rounded off to fit in the four-character display. Full values can be read
with other interfaces.
R: Read
W: Write
E: EEPROM
S: User
Set