Owner manual

Watlow EZ-ZONE
®
PM Integrated Controller 93 Chapter 6 Setup Page
Setup Page
Dis-
play
Parameter Name
Description
Range Default
Modbus Rela-
tive
Address
CIP
Class
Instance
Attribute
hex (dec)
Pro-
fibus
Index
Param-
eter ID
Data
Type
&
Read/
Write
[`FiL]
[ FiL]
Math (1)
Filter
Filtering smooths out
the output signal of this
function block. Increase
the time to increase fil-
tering.
0.0 to 60.0 seconds 0.0 Instance 1
Map 1 Map 2
- - - - 3054
0x7D (125)
1
0x1C (28)
- - - - 25028 float
RWES
[`sof]
[`set]
Special Output Function Menu
[``Fn]
[ Fn]
Special Output (1)
Function
Set the function to match
the device it will operate.
[`oFF] Off (62)
[`uA;C] Motorized Valve
(1508)
[`Co;C] Compressor Control
(1506)
Off Instance 1
Map 1 Map 2
- - - - 3856
0x87 (135)
1
9
181 35009 uint
RWES
[SFn;A]
[SFn.A]
Special Output (1)
Source Function A
Set the type of function
that will be used for this
source.
[nonE] None (61)
[PWr] Power (73)
[`h;Pr] Heat Power (160)
[`C;Pr] Cool Power (161)
None Instance 1
Map 1 Map 2
- - - - 3840
0x87 (135)
1
1
182 35001 uint
RWES
[`Si;A]
[ Si.A]
Special Output (1)
Source Instance A
Set the instance of the
function selected above.
1 to 2 1 Instance 1
Map 1 Map 2
- - - - 3844
0x87 (135)
1
3
183 35003 uint
RWES
[SFn;b]
[SFn.b]
Special Output (1)
Source Function B
Set the type of function
that will be used for this
source.
[nonE] None (61)
[PWr] Power (73)
[`h;Pr] Heat Power (160)
[`C;Pr] Cool Power (161)
None Instance 1
Map 1 Map 2
- - - - 3842
0x87 (135)
1
2
184 35002 uint
RWES
[`Si;B]
[ Si.b]
Special Output (1)
Source Instance B
Set the instance of the
function selected above.
1 to 2 1 Instance 1
Map 1 Map 2
- - - - 3846
0x87 (135)
1
4
185 35004 uint
RWES
[Pon;A]
[Pon.A]
Special Output (1)
Power On Level 1
Compressor 1 power on
level.
-100.00 to 100.00% 0 Instance 1
Map 1 Map 2
- - - - 3874
0x87 (135)
1
0x12 (18)
186 35018 float
RWES
[PoF;A]
[PoF.A]
Special Output (1)
Power Off Level 1
Compressor 1 power off
level.
-100.00 to 100.00% 5 Instance 1
Map 1 Map 2
- - - - 3876
0x87 (135)
1
0x13 (19)
187 35019 float
RWES
[Pon;b]
[Pon.b]
Special Output (1)
Power On Level 2
Compressor 2 power on
level.
-100.00 to 100.00% 0 Instance 1
Map 1 Map 2
- - - - 3878
0x87 (135)
1
0x14 (20)
188 35020 float
RWES
[PoF;b]
[PoF.b]
Special Output (1)
Power Off Level 2
Compressor 1 power off
level.
-100.00 to 100.00% 5 Instance 1
Map 1 Map 2
- - - - 3880
0x87 (135)
1
0x15 (21)
189 35021 float
RWES
[`on;t]
[ on.t]
Special Output (1)
On Time
At a minimum stay on
specified amount of time.
0 to 9,999 seconds 20 Instance 1
Map 1 Map 2
- - - - 3882
0x87 (135)
1
0x16 (22)
190 35022 uint
RWES
Note:
Some values will be rounded off to fit in the four-character display. Full values can be read
with other interfaces.
R: Read
W: Write
E: EEPROM
S: User
Set