Owner manual

Watlow EZ-ZONE
®
PM Integrated Controller 94 Chapter 6 Setup Page
Setup Page
Dis-
play
Parameter Name
Description
Range Default
Modbus Rela-
tive
Address
CIP
Class
Instance
Attribute
hex (dec)
Pro-
fibus
Index
Param-
eter ID
Data
Type
&
Read/
Write
[`oF;t]
[ oF.t]
Special Output (1)
Off Time
At a minimum stay off
specified amount of time.
0 to 9,999 seconds 20 Instance 1
Map 1 Map 2
- - - - 3884
0x87 (135)
1
0x17 (23)
191 35023 uint
RWES
[``t;t]
[ t.t]
Special Output (1)
Valve Travel Time
The amount of time it
takes the valve to fully
open and then fully close.
10 to 9,999 seconds 120 Instance 1
Map 1 Map 2
- - - - 3886
0x87 (135)
1
0x18 (24)
192 35024 uint
RWES
[``db]
[ db]
Special Output (1)
Dead Band
Output power needs to
change by specified level
prior to turning on.
1.0 to 100.0% 2 Instance 1
Map 1 Map 2
- - - - 3888
0x87 (135)
1
0x19 (25)
193 35025 float
RWES
[`t;dL]
[ t.dL]
Special Output (1)
Time Delay
If requested power is
0.0% for longer than the
specified Time Delay, the
compressor will shut off.
0 to 9,999 seconds 0 Instance 1
Map 1 Map 2
- - - - 3890
0x87 (135)
1
0x1A (26)
- - - - 35026 uint
RWES
[`FUn]
[`Set]
Function Key
`leu]
[ LEv]
Function Key (3 to 4)
Active Level
The Function Key will
always power up in the
low state.
Pressing the Function
Key will toggle the se-
lected action.
high] High (37)
[Low] Low (53)
High Instance 3
Map 1 Map 2
1360 1600
Instance 4
Map 1 Map 2
1380 1620
0x6E (110)
3 to 4
1
137 10001 uint
RWES
Note:
Some values will be rounded off to fit in the four-character display. Full values can be read
with other interfaces.
R: Read
W: Write
E: EEPROM
S: User
Set