Owner manual

Watlow EZ-ZONE
®
PM Integrated Controller 95 Chapter 6 Setup Page
Setup Page
Dis-
play
Parameter Name
Description
Range Default
Modbus Rela-
tive
Address
CIP
Class
Instance
Attribute
hex (dec)
Pro-
fibus
Index
Param-
eter ID
Data
Type
&
Read/
Write
[``Fn]
[ Fn]
Function Key (1 to 2)
Action Function
Program the EZ Key to
trigger an action.
Functions respond to a
level state change or an
edge level change.
Note:
The Limit Reset func-
tion is not available in
firmware revision 11.0
and above.
[none] None (61)
[`r;en] Remote Set Point en-
able (216)
[LMr] Limit Reset, edge trig-
gered (82)
[usr;r] User Set Restore, edge
triggered (227)
[P;LoC] Keypad Lockout, level
triggered (217)
[ALM] Alarm Reset, edge
triggered (6)
[`SiL] Silence Alarms, edge
triggered (108)
[`AoF] Control Loops Off and
Alarms to Non-alarm State,
level triggered (220)
[`F;AL] Force Alarm to occur,
level triggered (218)
[idLE] Idle Set Point, level
triggered (107)
[tUnE] Tune, edge triggered
(98)
[MAn] Manual, level trig-
gered (54)
[`oFF] Switch Control Loop
Off, level triggered (90)
[`t;da] TRU-TUNE+
®
Dis-
able, level triggered (219)
[P;diS] Profile Disable, level
triggered (206)
[P;hoL] Profile Hold/Resume,
level triggered (207)
[ProF] Start Profile, edge
triggered (196)
[P;StS] Profile Start/Stop,
level triggered (208)
[s;stp] Start Step (1077)
None Instance 1
Map 1 Map 2
1364 1604
Instance 2
Map 1 Map 2
1384 1624
0x6E (110)
3 to 4
3
138 10003 uint
RWES
[``Fi]
[ Fi]
Function Key (1 to 2)
Function Instance
Select which instance the
EZ Key will affect. If only
one instance is avail-
able, any selection will
affect it.
1 to 4 0 Instance 1
Map 1 Map 2
1366 1606
Instance 2
Map 1 Map 2
1386 1626
0x96 (110)
3 to 4
4
139 10004 - - - -
[gLbL]
[`Set]
Global Menu
[`C_F]
[ C_F]
Global
Display Units
Select which scale to use
for temperature.
[```F] °F (30)
[```C] °C (15)
°F Instance 1
Map 1 Map 2
1838 2308
0x67 (103)
1
5
110 3005
uint
RWES
Note:
Some values will be rounded off to fit in the four-character display. Full values can be read
with other interfaces.
R: Read
W: Write
E: EEPROM
S: User
Set
Note:
When changing IP address the control power must be cycled for the new address to take effect.