User guide

Watlow EZ-ZONE
®
PM PID Controller 17 Chapter 2 Install and Wire
Warning: Óç
Use National Electric (NEC) or other
country-specific standard wiring and
safety practices when wiring and
connecting this controller to a power
source and to electrical sensors or
peripheral devices. Failure to do so
may result in damage to equipment
and property, and/or injury or loss
of life.
Note:
Maximum wire size termination and
torque rating:
0.0507 to 3.30 mm
2
(30 to 12
AWG) single-wire termination or
two 1.31 mm
2
(16 AWG)
0.8 Nm (7.0 lb.-in.) torque
Note:
Adjacent terminals may be labeled
differently, depending on the model
number.
Note:
To prevent damage to the control-
ler, do not connect wires to unused
terminals.
Note:
Maintain electrical isolation between
analog input 1, digital input-outputs,
switched dc/open collector outputs
and process outputs to prevent
ground loops.
Note:
The control output common termi-
nal and the digital common terminal
are referenced to different voltages
and must remain isolated.
Note:
This Equipment is suitable for use in
CLASS I, DIVISION 2, Groups A, B,
C and D or Non-Hazardous locations
only. Temperature Code T4A
Warning:
ç
Explosion Hazard - Dry contact clo-
sure Digital Inputs shall not be used
in Class I Division 2 Hazardous Loca-
tions unless switch used is approved
for this application.
Warning:
ç
Explosion Hazard – Substitution of
component may impair suitability
for
CLASS I, DIVISION 2.
Warning:
ç
Explosion Hazard - Do not discon-
nect while the circuit is live or
unless the area is known to be free
of ignitable concentrations of flam-
mable substances.
Input 1 Thermocouple
-
+
S1
R1
Slot A
• 2kΩmaximumsourceresistance
• >20MΩinputimpedance
• 3microampereopen-sensordetection
• Thermocouplesarepolaritysensitive.Thenegativelead(usually
red) must be connected to S1.
• Toreduceerrors,theextensionwireforthermocouplesmustbe
of the same alloy as the thermocouple.
PM _ _ _ _ _-_ AAAA _ _
Input 1 RTD
2-wire
S1
R1
S1
S3
Slot A
3-wire
T1
S1
R1
S1
S2
S3
Slot A
• platinum,100and1,000Ω@0°C
• calibrationtoDINcurve(0.00385Ω/Ω/°C)
• 20Ωtotalleadresistance
• RTDexcitationcurrentof0.09mAtypical.Each
ohm of lead resistance may affect the reading by
0.03°C.
• For3-wireRTDs,theS1lead(usuallywhite)must
be connected to R1.
• Forbestaccuracyusea3-wireRTDtocompensate
for lead-length resistance. All three lead wires must
have the same resistance.
PM _ _ _ _ _-_ AAAA _ _
Input 1 Process
-
+
S1
R1
volts
Slot A
-
+
T1
S1
amperes
Slot A
• 0to20mA@100Ωinputimpedance
• 0to10VÎ(dc)@20kΩinputimpedance
• 0to50mVÎ(dc)@20kΩinputimpedance
• scalable
PM _ _ _ _ _-_ AAAA _ _
Input 1 Potentiometer
S1
R1
Slot A
CW
CCW
• Usea1kΩpotentiometer.
PM _ _ _ _ _-_ AAAA _ _