User guide

Watlow EZ-ZONE
®
PM PID Controller 37 Chapter 5 Operations Page
Operations Page
Display
Parameter Name
Description
Range Default
Modbus Rela-
tive Address
CIP
Class
Instance
Attribute
hex (dec)
Pro-
fibus
Index
Param-
eter ID
Data
Type
&
Read/
Write
[``o;u]
[ o.v]
Linearization (1)
Output Value
View the value of this
function's output.
-1,999.000 to
9,999.000°F or units
-1,128.000 to
5,537.000°C
- - - - Instance 1
Map 1 Map 2
- - - - 3572
0x86 (134)
1
7
- - - - 34007 float
R
No Dis-
play
Linearization (1)
Output Error
View reported cause for
Linearization output mal-
function.
None (61)
Open (65)
Shorted (127)
Measurement error
(140)
Bad calibration data
(139)
Ambient error (9)
RTD error (14)
Fail (32)
Math error (1423)
Not sourced (246)
Stale (1617)
Can't process (1659)
- - - - Instance 1
Map 1 Map 2
- - - - 3614
0x86 (134)
1
0x1C (28)
- - - - 34028 uint
R
[``Pu]
[oPEr]
Process Value Menu
[`Su;A]
[ Sv.A]
Process Value (1)
Source Value A
View the value of Source A.
Linearization 1 is connect-
ed to Source A of Process
Value 1
-1,999.000 to
9,999.000°F or units
-1,128.000 to
5,537.000°C
- - - - Instance 1
Map 1 Map 2
- - - - 3310
0x7E (126)
1
0x10 (16)
- - - - 26016 float
R
[oFSt]
[oFSt]
Process Value (1)
Offset
Set an offset to be applied
to this function's output.
-1,999.000 to
9,999.000°F or units
-1,128.000 to
5,537.000°C
0 Instance 1
Map 1 Map 2
- - - - 3324
0x7E (126)
1
0x17 (23)
- - - - 26023 float
RWES
[``o;u]
[ o.v]
Process Value (1)
Output Value
View the value of this func-
tion block's output.
-1,999.000 to
9,999.000°F or units
-1,128.000 to
5,537.000°C
- - - - Instance 1
Map 1 Map 2
- - - - 3322
0x7E (126)
1
0x16 (22)
- - - - 26022 float
R
No Dis-
play
Process Value (1)
Output Error
View reported cause for
Process output malfunc-
tion.
[none] None (61)
[open] Open (65)
[shrt] Shorted (127)
[`e;m] Measurement
error (140)
[e;Cal] Bad calibra-
tion data (139)
[er;ab] Ambient er-
ror (9)
[e;rtd] RTD error (14)
[fail] Fail (32)
[e;rm] Math error
(1423)
[Nsrc] Not sourced
(246)
[stal] Stale (1617)
[no;pr] Can't process
(1659)
- - - - Instance 1
Map 1 Map 2
- - - - 3332
0x86 (134)
1 to 2
0x1B (27)
- - - - 26027 uint
R
Note:
Some values will be rounded off to fit in the four-character display. Full values can be
read with other interfaces.
R: Read
W: Write
E: EE-
PROM
S: User
Set