User guide

Watlow EZ-ZONE
®
PM PID Controller 38 Chapter 5 Operations Page
Operations Page
Display
Parameter Name
Description
Range Default
Modbus Rela-
tive Address
CIP
Class
Instance
Attribute
hex (dec)
Pro-
fibus
Index
Param-
eter ID
Data
Type
&
Read/
Write
[`dio]
[oPEr]
Digital Input/Output Menu
[`do;S]
[ do.S]
Digital Output (5 to 6)
Output State
View the state of this out-
put.
[`off] Off (62)
[``on] On (63)
- - - - Instance 5
Map 1 Map 2
1012 1132
Offset to next
instance equals
+30
0x6A (106)
5 to 6
7
90 6007 uint
R
[`di;S]
[ di.S]
Digital Input (5 to 6)
Input State
View this event input state.
[`off] Off (62)
[``on] On (63)
- - - - Instance 5
Map 1 Map 2
1020 1140
Offset to next
instance equals
+30
0x6A (106)
5 to 6
0xB (11)
- - - - 6011 uint
R
[`ei;S]
[ Ei.S]
Digital Input (5 to 6)
Event Status
View this event input state.
[`iact] Inactive (41)
[``act] Active (5)
- - - - Instance 5
Map 1 Map 2
1328 1568
Offset to next
instance equals
+20
0x6E (110)
5 to 6
5
140 10005 uint
R
No Dis-
play
EZ-Key/s (1 to 2)
Event Status
View this event input state.
[`iact] Inactive (41)
[``act] Active (5)
- - - - Instance 1
Map 1 Map 2
1368 1608
Instance 2
Map 1 Map 2
- - - - 1628
0x6E (110)
3 to 4
5
140 10005 uint
R
[Mon]
[oPEr]
Monitor Menu
[C;MA]
[C.MA]
Monitor (1)
Control Mode Active
View the current control
mode.
[`off] Off (62)
[AUto] Auto (10)
[MAn] Manual (54)
Off
Instance 1
Map 1 Map 2
1882 2362
0x97 (151)
1
2
- - - - 8002 uint
R
[`h;Pr]
[ h.Pr]
Monitor (1)
Heat Power
View the current heat out-
put level.
0.0 to 100.0% 0.0
Instance 1
Map 1 Map 2
1904 2384
0x97 (151)
1
0xD (13)
- - - - 8011 float
R
[`C;Pr]
[ C.Pr]
Monitor (1)
Cool Power
View the current cool out-
put level.
-100.0 to 0.0% 0.0
Instance 1
Map 1 Map 2
1906 2386
0x97 (151)
1
0xE (14)
- - - - 8014 float
R
[`C;SP]
[ C.SP]
Monitor (1)
Closed Loop Set Point
View the set point cur-
rently in effect.
-1,999.000 to
9,999.000°F or units
-1,128.000 to
5,537.000°C
- - - - Instance 1
Map 1 Map 2
2172 2652
0x6B (107)
1
7
- - - - 8029 float
R
[`Pu;A]
[ Pv.A]
Monitor (1)
Process Value Active
View the current filtered
process value using the
control input.
-1,999.000 to
9,999.000°F or units
-1,128.000 to
5,537.000°C
- - - - Instance 1
Map 1 Map 2
402 402
0x68 (104)
1
0x16 (22)
- - - - 8031 float
R
Note:
Some values will be rounded off to fit in the four-character display. Full values can be
read with other interfaces.
R: Read
W: Write
E: EE-
PROM
S: User
Set