User guide

Watlow EZ-ZONE
®
PM PID Controller 43 Chapter 5 Operations Page
Operations Page
Display
Parameter Name
Description
Range Default
Modbus Rela-
tive Address
CIP
Class
Instance
Attribute
hex (dec)
Pro-
fibus
Index
Param-
eter ID
Data
Type
&
Read/
Write
[P;Sta]
[oPEr]
Profile Status Menu
Profile Menu appears if:
(PM _ [R, B*, N, E*] _ _ _-_ _ _ _ _ _ _)
* Available with PM8/9 only
* Some parameters in the Profile Status Menu can be changed for the
currently running profile, but should only be changed by knowledge-
able personnel and with caution. Changing parameters via the Pro-
file Status Menu will not change the stored profile but will have an
immediate impact on the profile that is running.
Changes made to profile parameters in the Profiling Pages will be
saved and will also have an immediate impact on the running pro-
file.
[P;Str]
[P.Str]
Profile Status
Profile Start
Select step to act upon.
1 to 40 1 Instance 1
Map 1 Map 2
2520 4340
0x7A (122)
1
1
204 22001 uint
RW
[P;ACr]
[PACr]
Profile Status
Action Request
[nonE] None (61)
[step] Step Start (89)
[`End] Terminate
(148)
[rESU] Resume (147)
[PAUS] Pause (146)
[ProF] Profile (77)
None Instance 1
Map 1 Map 2
2540 4360
0x7A (122)
1
0xB (11)
205 22011 uint
RW
[`StP]
[ StP]
Profile Status
Step
View the currently run-
ning step.
1 to 40 0 (none) Instance 1
Map 1 Map 2
2526 4346
0x7A (122)
1
4
- - - - 22004 uint
R
[S;typ]
[S.typ]
Profile Status
Step Type
View the currently run-
ning step type.
UStP] Unused Step
(50)
[`End] End (27)
[``JL] Jump Loop
(116)
[CloC] Wait For Time
(1543)
[W;bo] Wait For Both
(210)
[W;Pr] Wait For Pro-
cess (209)
[`W;E] Wait For Event
(144)
[SoAH] Soak (87)
[``ti] Time (143)
[rAtE] Rate (81)
- - - - Instance 1
Map 1 Map 2
2544 4364
0x7A (122)
1
0xD (13)
- - - - 22013 uint
R
[t;SP1]
[tg.SP]
Profile Status
*Target Set Point Loop 1
View or change the target
set point of the current
step.
-1,999.000 to
9,999.000°F or units
-1,128.000 to
5,537.000°C
0.0°F
or
units
-18.0°C
Instance 1
Map 1 Map 2
2542 4502
0x7A (122)
1
0xC (12)
- - - - 22012 uint
RW
[aC;sp]
[AC.SP]
Profile Status
Produced Set Point 1
Display the current set
point, even if the profile is
ramping.
-1,999.000 to
9,999.000°F or units
-1,128.000 to
5,537.000°C
0.0°F
or
units
-18.0°C
Instance 1
Map 1 Map 2
2528 4348
- - - - - - - - 22005 float
R
[hoUr]
[hoUr]
Profile Status
Hours
Step time remaing in
hours.
0 to 99 0 Instance 1
Map 1 Map 2
- - - - 4494
0x7A (122)
1
0x4E (78)
- - - - 22078 uint
RW
Note:
Some values will be rounded off to fit in the four-character display. Full values can be
read with other interfaces.
R: Read
W: Write
E: EE-
PROM
S: User
Set