User guide

Watlow EZ-ZONE
®
PM PID Controller 51 Chapter 6 Setup Page
Setup Page
Dis-
play
Parameter Name
Description
Range Default
Modbus Rela-
tive
Address
CIP
Class
Instance
Attribute
hex (dec)
Pro-
fibus
Index
Param-
eter ID
Data
Type
&
Read/
Write
[`iP;9]
[ ip.9]
Linearization (1)
Input Point 9
Set the value that will be
mapped to output 9.
-1,999.000 to 9,999.000 8.0 Instance 1
Map 1 Map 2
- - - - 3590
0x86 (134)
1
0x10 (16)
173 34016 float
RWES
[`oP;9]
[ op.9]
Linearization (1)
Output Point 9
Set the value that will be
mapped to input 9.
-1,999.000 to 9,999.000 8.0 Instance 1
Map 1 Map 2
- - - - 3610
0x86 (134)
1
0x1A (26)
174 34026 float
RWES
[iP;10]
[ip.10]
Linearization (1)
Input Point 10
Set the value that will be
mapped to output 10.
-1,999.000 to 9,999.000 9.0 Instance 1
Map 1 Map 2
- - - - 3592
0x86 (134)
1
0x11 (17)
175 34017 float
RWES
[oP;10]
[op.10]
Linearization (1)
Output Point 10
Set the value that will be
mapped to input 10.
-1,999.000 to 9,999.000 9.0 Instance 1
Map 1 Map 2
- - - - 3612
0x86 (134)
1
0x1B (27)
176 34027 float
RWES
[``Pu]
[`Set]
Process Value Menu
[``Fn]
[ Fn]
Process Value (1)
Function
Set the function that will
be applied to the source or
sources.
[`oFF] Off (62)
[`alt] *Pressure to Alti-
tude (1649)
Off Instance 1
Map 1 Map 2
- - - - 3320
0x7E (126)
1
0x15 (21)
123 26021 uint
RWES
[p;unt]
[P.unt]
Process Value (1)
Pressure Units*
Set the units that will be
applied to the source.
[`psi] Pounds per Square
Inch (1671)
[pasc] Pascal (1674)
[atm] Atmosphere (1675)
[mbr] Millibar (1672)
[torr] Torr (1673)
PSI Instance 1
Map 1 Map 2
- - - - 3334
0x7E (126)
1
0x1C (28)
- - - - 26028 uint
RWES
[a;unt]
[A.unt]
Process Value (1)
Altitude Units*
Set the units that will be
applied to the source.
[`Hft] Kilofeet (1677)
[``ft] Feet (1676)
HFt Instance 1
Map 1 Map 2
- - - - 3336
0x7E (126)
1
0x1D (29)
- - - - 26029 uint
RWES
[`Fil]
[ FiL]
Process Value (1)
Filter
Filtering smooths out the
output signal of this func-
tion block. Increase the
time to increase filtering.
0.0 to 60.0 seconds 0.0 Instance 1
Map 1 Map 2
- - - - 3330
0x7E (126)
1
0x1A (26)
- - - - 26026 float
RWES
Note:
Some values will be rounded off to fit in the four-character display. Full values can be
read with other interfaces.
R: Read
W: Write
E: EE-
PROM
S: User
Set
* Pressure Altitude calculation is based on the International Standard Atmosphere, 1976