User guide

Watlow EZ-ZONE
®
PM PID Controller 52 Chapter 6 Setup Page
Setup Page
Dis-
play
Parameter Name
Description
Range Default
Modbus Rela-
tive
Address
CIP
Class
Instance
Attribute
hex (dec)
Pro-
fibus
Index
Param-
eter ID
Data
Type
&
Read/
Write
[`dio]
[`Set]
Digital Input/Output Menu
[`dir]
[ dir]
Digital Input/Output (5
to 6)
Digital I/O Direction
Set this function to oper-
ate as an input or output.
[OtPt] Output (68)
[iCon] Input Dry Contact
(44)
[``in] Input Voltage (193)
Output Instance 5
Map 1 Map 2
1000 1120
Offset to next
instance (Map
1 & Map 2)
equals +30
0x6A (106)
5 to 6
1
82 6001 uint
RWES
[``Fn]
[ Fn]
Digital Output (5 to 6)
Output Function
Select what function will
drive this output.
[`oFF] Off (62)
[lim] Limit (126)
[Ent;b] Profile Event Out
B (234)
[Ent;A] Profile Event Out
A (233)
[SoF;2] Special Function
Output 2 (1533)
[SoF;1] Special Function
Output 1 (1532)
[CooL] Cool (20)
[heat] Heat (36)
[ALM] Alarm (6)
Off Instance 5
Map 1 Map 2
1008 1128
Offset to next
instance (Map
1 & Map 2)
equals +30
0x6A (106)
5 to 6
5
83 6005 uint
RWES
[``Fi]
[ Fi]
Digital Output (5 to 6)
Output Function In-
stance
Set the instance of the
function selected above.
1 to 4 1 Instance 5
Map 1 Map 2
1010 1130
Offset to next
instance (Map
1 & Map 2)
equals +30
0x6A (106)
5 to 6
6
84 6006 uint
RWES
[`o;Ct]
[ o.Ct]
Digital Output (5 to 6)
Output Control
Set the output control
type. This parameter
is only used with PID
control, but can be set
anytime.
[`Ftb] Fixed Time Base
(34)
[`utb] Variable Time
Base (103)
Fixed
Time
Base
Instance 5
Map 1 Map 2
1002 1122
Offset to next
instance (Map
1 & Map 2)
equals +30
0x6A (106)
5 to 6
2
85 6002 uint
RWES
[`o;tb]
[ o.tb]
Digital Output (5 to 6)
Output Time Base
Set the time base for
fixed-time-base control.
[ 0.1 for Fast and Bi-Di-
rectional outputs, 5.0 for
Slow outputs] to 60
- - - - Instance 5
Map 1 Map 2
1004 1124
Offset to next
instance (Map
1 & Map 2)
equals +30
0x6A (106)
5 to 6
3
86 6003 float
RWES
Note:
Some values will be rounded off to fit in the four-character display. Full values can be
read with other interfaces.
R: Read
W: Write
E: EE-
PROM
S: User
Set