User guide

Watlow EZ-ZONE
®
PM PID Controller 60 Chapter 6 Setup Page
Setup Page
Dis-
play
Parameter Name
Description
Range Default
Modbus Rela-
tive
Address
CIP
Class
Instance
Attribute
hex (dec)
Pro-
fibus
Index
Param-
eter ID
Data
Type
&
Read/
Write
[`o;hi]
[ o.hi]
Output Digital (1 to 2)
Output High Power
Scale
The power output will
never be greater than
the value specified and
will represent the value
at which output scaling
stops.
0.0 to 100.0% 100.0% Instance 1
Map 1 Map 2
898 1018
Offset to next
instance (Map
1 & Map 2)
equals +30
0x6A (106)
1 to 2
0xA (10)
88 6010 float
RWES
[`o;ty]
[ o.ty]
Output Process (1)
Output Type
Select whether the pro-
cess output will operate in
volts or milliamps.
[uoLt] Volts (104)
[`MA] Milliamps (112)
Volts Instance 1
Map 1 Map 2
720 840
0x76 (118)
1
1
95 18001 uint
RWES
[``Fn]
[ Fn]
Output Process (1)
Output Function
Set the type of function
that will drive this out-
put.
[`oFF] Off (62)
[dupl] Duplex (212)
[Cool] Cool (20)
[heat] Heat (36)
[rmt] Retransmit (213)
[Ent;b] Profile Event Out
B (234)
[Ent;A] Profile Event Out
A (233)
[ALM] Alarm (6)
Off Instance 1
Map 1 Map 2
722 842
0x76 (118)
1
2
96 18002 uint
RWES
[`r;Sr]
[ r.Sr]
Output Process (1)
Retransmit Source
Select the value that will
be retransmitted.
[``Ai] Analog Input (142)
[StPt] Set Point (85)
[CUrr] Current (22)
[``Pu] Process Value
(241)
Analog
Input
Instance 1
Map 1 Map 2
724 844
0x76 (118)
1
3
97 18003 uint
RWES
[``Fi]
[ Fi]
Output Process (1)
Output Function In-
stance
Set the instance of the
function selected above.
1 to 4 1 Instance 1
Map 1 Map 2
726 846
0x76 (118)
1
4
98 18004 uint
RWES
[`S;Lo]
[ S.Lo]
Output Process (1)
Scale Low
Set the scale low for pro-
cess output in electrical
units. This value; in volts
or milliamps, will cor-
respond to 0% PID power
output or range low re-
transmit output.
-100.0 to 100.0 0.00 Instance 1
Map 1 Map 2
736 856
0x76 (118)
1
9
99 18009 float
RWES
[`S;hi]
[ S.hi]
Output Process (1)
Scale High
Set the scale high for pro-
cess output in electrical
units. This value; in volts
or milliamps, will corre-
spond to 100% PID power
output or range high
retransmit output. .
-100.0 to 100.0 10.00 Instance 1
Map 1 Map 2
738 858
0x76 (118)
1
0xA (10)
100 18010 float
RWES
Note:
Some values will be rounded off to fit in the four-character display. Full values can be
read with other interfaces.
R: Read
W: Write
E: EE-
PROM
S: User
Set