User guide

Watlow EZ-ZONE
®
PM PID Controller 68 Chapter 6 Setup Page
Setup Page
Dis-
play
Parameter Name
Description
Range Default
Modbus Rela-
tive
Address
CIP
Class
Instance
Attribute
hex (dec)
Pro-
fibus
Index
Param-
eter ID
Data
Type
&
Read/
Write
[Ad;M]
[Ad.M]
Communications (1)
Modbus Address
Set the network address
of this controller. Each de-
vice on the network must
have a unique address.
1 to 247 1 Instance 1
Map 1 Map 2
2482 2962
0x96 (150)
1
2
- - - - 17007 uint
RWE
[bAUd]
[bAUd]
Communications (1)
Baud Rate
Set the speed of this con-
troller's communications
to match the speed of the
Modbus serial network.
[9600] 9,600 (188)
[`19;2] 19,200 (189)
[`38;4] 38,400 (190)
9,600 Instance 1
Map 1 Map 2
2484 2964
0x96 (150)
1
3
- - - - 17002 uint
RWE
[`PAr]
[ PAr]
Communications
Parity (1)
Set the parity of this con-
troller to match the par-
ity of the Modbus serial
network.
[none] None (61)
[EuEn] Even (191)
[`odd] Odd (192)
None Instance 1
Map 1 Map 2
2486 2966
0x96 (150)
1
4
- - - - 17003 uint
RWE
[`C_f]
[ C_F]
Communications (1)
Display Units
Select whether this com-
munications channel
will display in Celsius or
Fahrenheit.
Note:
Applies to Modbus only.
[```f] Fahrenheit (30)
[```C] Celsius (15)
F Instance 1
Map 1 Map 2
2490 2970
0x96 (150)
1
6
- - - - 17050 uint
RWE
[M;hL]
[M.hL]
Communications (1)
Modbus Word Order
Select the word order of
the two 16-bit words in
the floating-point values.
[Lohi] Low-High (1331)
[hiLo] High-Low (1330)
Low-High Instance 1
Map 1 Map 2
2488 2968
0x96 (150)
1
5
- - - - 17043 uint
RWE
[Map]
[ Map]
Communications (1)
Data Map
If set to 1 the control will
use PM legacy mapping.
If set to 2 the control will
use new mapping to ac-
commodate new functions.
1 to 2 If 9
th
dig-
it of part
number
is a 1, 2,
3 or D.
- - - - - - - - - - - - 17059 - - - -
[`nU;S]
[ nV.S]
Communications (1)
Non-Volatile Save
If set to Yes all values
written to the control will
be saved in EEPROM.
[`yes] Yes (106)
[``no] No (59)
Yes Instance 1
Map 1 Map 2
2494 2974
0x96 (150)
1
8
198 17051 uint
RWE
[rtC] (Available with PM4, PM8 and PM9 models only)
[`SEt]
Real Time Clock Menu
[hoUr]
[hoUr]
Real Time Clock
Hours
Set the current time.
0 to 23 0 Instance 1
Map 1 Map 2
- - - - 4004
88 (136)
1
3
- - - - 36003 uint
RW
Note:
Some values will be rounded off to fit in the four-character display. Full values can be
read with other interfaces.
R: Read
W: Write
E: EE-
PROM
S: User
Set
* Available with PM4, PM8 and PM9 models only