User guide

Watlow EZ-ZONE
®
PM PID Controller 82 Chapter 8 Factory Page
Factory Page
Dis-
play
Parameter Name
Description
Range Default
Modbus
Relative Ad-
dress
CIP
Class
Instance
Attribute
hex (dec)
Profibus
Index
Param-
eter ID
Data
Type
&
Read/
Write
No Dis-
play
Diagnostics
Firmware ID
Display the Firmware ID.
0 to 2,147,483,647 - - - - Instance 1
Map 1 Map 2
2 2
0x65
(101)
1
2
- - - - 1002 dint
R
[`CAL]
[FCty]
Calibration Menu
[`Mu]
[ Mv]
Calibration (1 to 2)
Electrical Measurement
Read the raw electrical
value for this input in the
units corresponding to
the Sensor Type (Setup
Page, Analog Input Menu)
setting.
-3.4e38 to 3.4e38 - - - - Instance 1
Map 1 Map 2
400 400
Instance 2
Map 1 Map 2
480 490
0x68
(104)
1 to 2
0x15 (21)
- - - - 4021 float
R
[ELi;o]
[ELi.o]
Calibration (1 to 2)
Electrical Input Offset
Change this value to cali-
brate the low end of the
input range.
-1,999.000 to 9,999.000 0.0 Instance 1
Map 1 Map 2
378 378
Instance 2
Map 1 Map 2
458 468
0x68
(104)
1 to 2
0xA (10)
- - - - 4010 float
RWES
[ELi;S]
[ELi.S]
Calibration (1 to 2)
Electrical Input Slope
Adjust this value to cali-
brate the slope of the in-
put value.
-1,999.000 to 9,999.000 1.0 Instance 1
Map 1 Map 2
380 380
Instance 2
Map 1 Map 2
460 470
0x68
(104)
1 to 2
0xB (11)
- - - - 4011 float
RWES
[ELo;o]
[ELo.o]
Calibration (1 or 3)
Electrical Output Offset
Change this value to cali-
brate the low end of the
output range.
Menu 2 calibrates output
3.
-1,999.000 to 9,999.000 0.0
- - - - - - - - - - - - 18005 - - - -
[ELo;S]
[ELo.S]
Calibration (1 or 3)
Electrical Output Slope
Adjust this value to cali-
brate the slope of the out-
put value.
Menu 2 calibrates output
3.
-1,999.000 to 9,999.000 1.0
- - - - - - - - - - - - 18006 - - - -
[``Pn]
[ Pn]
Calibration (1 to 3)
Part Number
Displays current setting
for control model number.
[fCty] Factory
[User] User
Factory - - - - - - - - - - - - - - - - uint
R
[Code]
[CodE]
Calibration (1 to 3)
Public Key
Changes the control to a
PM Express or back to
original model number as
shown on the side of the
control.
[2501] PM Express
[`606] Factory model
number
4999 - - - - - - - - - - - - - - - - uint
RWES
Note:
Some values will be rounded off to fit in the four-character display. Full values can be
read with other interfaces.
If there is only one instance of a menu, no submenus will appear.
R: Read
W: Write
E: EEPROM
S: User
Set