Installation Manual

IS-WR-Control-TAC 1934 EDP# 1915448 © 2019 Watts
USA: Tel: (800) 276-2419 • Fax: (417) 864-8161 • Watts.com
Canada: Tel: (905) 332-4090 • Fax: (905) 332-7068 • Watts.ca
Latin America: Tel: +52 55 4122 0138 • Fax: (52) 81-8000-7091
• Watts.com
Limited Warranty: Watts (the “Company”) warrants each product to be free from defects in material and workmanship under normal usage for a period of one year from the date of original shipment.
In the event of such defects within the warranty period, the Company will, at its option, replace or recondition the product without charge.
THE WARRANTY SET FORTH HEREIN IS GIVEN EXPRESSLY AND IS THE ONLY WARRANTY GIVEN BY THE COMPANY WITH RESPECT TO THE PRODUCT. THE COMPANY MAKES NO OTHER
WARRANTIES, EXPRESS OR IMPLIED. THE COMPANY HEREBY SPECIFICALLY DISCLAIMS ALL OTHER WARRANTIES, EXPRESS OR IMPLIED, INCLUDING BUT NOT LIMITED TO THE IMPLIED
WARRANTIES OF MERCHANTABILITY AND FITNESS FOR A PARTICULAR PURPOSE.
The remedy described in the first paragraph of this warranty shall constitute the sole and exclusive remedy for breach of warranty, and the Company shall not be responsible for any incidental, special
or consequential damages, including without limitation, lost profits or the cost of repairing or replacing other property which is damaged if this product does not work properly, other costs resulting
from labor charges, delays, vandalism, negligence, fouling caused by foreign material, damage from adverse water conditions, chemical, or any other circumstances over which the Company has no
control. This warranty shall be invalidated by any abuse, misuse, misapplication, improper installation or improper maintenance or alteration of the product.
Some States do not allow limitations on how long an implied warranty lasts, and some States do not allow the exclusion or limitation of incidental or consequential damages. Therefore the above
limitations may not apply to you. This Limited Warranty gives you specific legal rights, and you may have other rights that vary from State to State. You should consult applicable state laws to
determine your rights. SO FAR AS IS CONSISTENT WITH APPLICABLE STATE LAW, ANY IMPLIED WARRANTIES THAT MAY NOT BE DISCLAIMED, INCLUDING THE IMPLIED WARRANTIES OF
MERCHANTABILITY AND FITNESS FOR A PARTICULAR PURPOSE, ARE LIMITED IN DURATION TO ONE YEAR FROM THE DATE OF ORIGINAL SHIPMENT.
Wiring Detail
Zone 1 LED
2.5A Fuse
Pump
Relay
+ -
Zone 2 LED Zone 3 LED Zone 4 LED Zone 5 LED Zone 6 LED
2-Wire Thermostat
Dry Contact Connections
Potential Free, Dry Contacts
Max 8 Amps per Contact
to control boilers, circulators,
or other devices.
Jumpers need to be ran from terminal 1 to 1
to allow a single thermostat to control multiple
actuators as a single zone.
Do Not jumper terminals 4, A, or B.
3-Wire Thermostat
With 24 VAC Power
2-Wire Actuators
24 V Only
Transformer
60 VA
+
24 V
- +
120 V
-
G L N
System
Circulator
Main Power
Supply
Boiler TT
- Never connect a power consuming 2-wire thermostat to the
control as damage to the thermostat and/or control may occur.
- The maximum total load per terminal block is 0.3 A, or 7.5 VA,
and/or 3 actuators.
- External 24/120 VAC 60 VA transformer (81009509) is recommended for
all applications.
- Never jumper terminal points 4, A or B on the zone terminal blocks as
this may cause damage to the thermostat, the controller or both.
- Control does not use the end-switch wires of a 4-wire actuator.
CAUTION:
Both Master and Slave controls are designed to operate with a dedicated
24 VAC power supply. Two dry contact relays are provided on each to control
external components such as circulators, boilers, or other devices. Each relay
can switch between 24 VAC and 120 VAC.