Installation Guide

Apply continuous
1
/2” beads
of sealant between all connec-
tions of panels and install with
tightly butted seams. Excess
sealant must be spread flat with
a putty knife. All seams and fas-
tener heads in the assembly are
covered with a secondary
1
/2
bead of sealant and spread flat.
The seams should be covered
3
/4” to 1” on either side of
seam. All fastener/washers are
covered with sealant stretching
1” over the washer edges.
wedi Niches are installed in
a cut out in the wedi wall and
attached with it's flange right
into the center of 16 o.c. studs.
wedi sealant is set along the
connection of wall to niche.
2 Fasteners each side of the
niche are set to create a flush
transition to the wall panels.
Another
1
/2” bead of wedi seal -
ant is spread over fasteners
and seams.
A continuous
1
/2” bead of
sealant is set into the channel
and along the vertical curb notch
part. A circle of
1
/2” sealant bead
is set against the wall panels
where the curb attaches. A
1
/2” x
1
/2” bed of thinset mortar is ap-
plied to the subfloor. The tightly
cut to fit curb is pressed into the
connection. Weight is applied on
and against the curb ( from out-
side) and another
1
/2” bead of
sealant is applied over all curb
seams and spread flat. The seams
must be covered
3
/4” to 1
either side of a seam.
9
11
10
12
All bottom perimeter joints,
curb joints, vertical and hori-
zontal panel joints are visibly
covered with wedi sealant.
Coverage should be continu-
ously visible for at least ¾” to
1” on each side of the joint.
No mastic adhesives are to be
used to install tile in wedi
shower systems.
Ceramic tiles smaller than
2”x 2” must be grouted using
epoxy grout. River Rock or
Pebble Stones must be
grouted with a modified
cementitious sanded grout.
Large format tile can be used
on wedi Fundo bases. The
tiles must be cut where the
slope fields meet unless a
single slope model is used.
After Installation
When complete wedi shower
system is installed with wedi
joint sealant, a water flood
test may be performed only
2 hours after final application
of wedi joint sealant (applica-
tion temperature must be
ambient / interior with nor-
mal relative humidity and
temperatures above 40°F).