User`s manual

32 | MW500
Troubleshooting and Maintenance
- English -
6 TROUBLESHOOTING AND MAINTENANCE
6.1 FAULT AND ALARMS
NOTE!
Refer to the quick reference and to the programming manual of the
MW500 for further information about each fault or alarm.
6.2 SOLUTIONS FOR THE MOST FREQUENT PROBLEMS
Table 6.1: Solutions for the most frequent problems
Problem Point to be verified Corrective Action
Motor will not
start
Incorrect wiring 1. Check all the power and command connections.
Analog reference
(if used)
1. Check if the external signal is properly connected.
2. Check the status of the control potentiometer (if used).
Wrong settings 1. Check if the parameter values are correct for the application.
Fault 1. Check if the drive is disabled due to a fault condition.
Motor stall 1. Decrease the motor overload.
2. Increase P0136, P0137 (V/f).
Motor speed
oscillates
Loose connections 1. Stop the drive, turn off the power supply and tighten all the
connections.
2. Check all the internal connections of the drive.
Defective speed
reference
potentiometer
1. Replace the potentiometer.
Oscillation of the
external analog
reference
1. Identify the cause of the oscillation. If the cause is electrical
noise, use shielded cables or separate them from the power
or command wiring.
2. Interconnect the GND of the analog reference to the grounding
connection of the drive.
Too high or too
low motor speed
Incorrect settings
(reference limits)
1. Check whether the content of P0133 (minimum speed) and
P0134 (maximum speed) are properly set for the used motor
and application.
Control signal of the
analog reference
(if used)
1. Check the level of the reference control signal.
2. Check the setting (gain and offset) of parameters P0232 to
P0240.
Motor nameplate 1. Check whether the motor used matches the application.
Display off HMIR connections 1. Check the connections of the drive external HMIR.
Power supply voltage 1. Rated values must be within the limits specified below:
380-480 V power supply: - Min: 323 V - Max: 528 V.
Main supply fuse open 1. Replace the fuses.