Instructions
Detailed descriptions of I/O modules | Digital counter module UR20-2CNT-100
156 1432790000/03/02.2014Manual u-remote
Primary counting direction down
– Down-counting from the load value
– If the end value -1 is reached during counting in the nega-
tive direction, the counter jumps to the load value at the
next count pulse and the internal gate is automatically
closed. In addition, a process alarm can be triggered if it
is parametrized.
– To restart the counting process, the internal gate must be
reopened and the counting starts at the load value
– It is possible to count beyond the upper count limit
Countingrange
Limits Validrangeofvalues
Lower count limit –2 147 483 647 (–2
31
) to +2 147 483 646 (2
31
–2)
Upper count limit +2 147 483 648 (2
31
–1)
Upper
count limit
Load value
End value
Gate start Gate startAutomatic
gate stop
Automatic
gate stop
Counter state
0
Time
1-timecounting,primarycountingdirectiondown.
Periodic counting
No primary counting direction
– Counting starting at the load value, up or down.
– Upon reaching the corresponding count limit, the counter
jumps to the load value and starts counting again from
there. In addition, a process alarm can be triggered if it is
parametrized.
– Because of the register size, the count limits are xed and
cannot be changed.
Countingrange
Limits Validrangeofvalues
Lower count limit –2 147 483 648 (–2
31
)
Upper count limit +2 147 483 647 (2
31
–1)
Upper
count limit
Lower
count limit
Load value
Zero
crossing
Overrun
Underrun
Gate start Gate stop
Counter state
0
Time
Periodiccounting,noprimarycountingdirection.
Primary counting direction up
– Up-counting starting at the load value
– If the end value -1 is reached during counting in the posi-
tive direction, the counter jumps to the load value at the
next positive count pulse and continues counting from
there. In addition, a process alarm can be triggered if it is
parametrized.
– It is possible to count beyond the lower count limit.
Countingrange
Limits Validrangeofvalues
Lower count limit –2 147 483 647 (–2
31
+1) to +2 147 483 647 (2
31
–1)
Upper count limit +2 147 483 648 (2
31
)
Upper
count limit
Lower
count limit
Load value
Overrun
Underrun
Gate start Gate stop
Counter state
0
Time
Periodiccounting,primarycountingdirectionup.