Instructions

Conguration| Parameter overview
30 1432790000/03/02.2014Manual u-remote
Overview of the editable parameters
Product Order No. Parameter Optional values Default value
Ch 0: Process alarm latch value disabled (0) / enabled (1) disabled
Ch 0: Counting mode count endless (0) / once - forward (1) /
once - backwards (2) / once - no main
direction (3) / periodic - forward (4) /
periodic - backwards (5) / periodic - no
main direction (6)
count endless
Ch 0: Condition for DO disabled (0) / higher equal comparison
value (1) / lower equal comparison value
(2)/ equal comparison value (3)
disabled
Ch 0: Counter dir. signal B inv. disabled (0) / enabled (1) disabled
Ch 0: Reset disabled (0) / high level (1) / rising edge
0-1 (2)/ rising edge once 0-1 (3)
disabled
Ch 0: Signal mode Rotary transducer - single (0) / Rotary
transducer - double (1) / Rotary trans- (1) / Rotary trans-Rotary trans-
ducer - quadruple (2) / Pulse and Direction
(3) / disabled (4)
disabled
Ch 0: HW gate disabled (0) / enabled (1) disabled
Ch 0: Counter behaviour internal gate Interrupt counting (0) / Cancel counting
(1)
interrupt counting
Ch 0: End value -2147483648 ... 2147483647 2147483647
Ch 0: Load value -2147483648 ... 2147483647 0
Ch 0: Hysteresis 0 ... 255 0
Ch 0: Pulse duration 0 ... 255 [Input value x 2 = output time;
corresponds to 0 ... 510ms]
0
UR20-2CNT-100
1315590000 Diagnostic alarm disabled (0) / enabled (1) disabled
Ch 0 ... Ch1: Filter time signal A 0,01 ms [100kHz] (0) / 0,017 ms
[50kHz] (1) / 0,033 ms [30kHz] (2) /
0,1 ms [10kHz] (3) / 0,2 ms [5kHz] (4) /
0,5 ms [2kHz] (5) / 1 ms [1kHz] (6)
0,01 ms
Ch 0 ... Ch1: Filter time signal B 0,01 ms [100kHz] (0) / 0,017 ms
[50kHz] (1) / 0,033 ms [30kHz] (2) /
0,1 ms [10kHz] (3) / 0,2 ms [5kHz] (4) /
0,5 ms [2kHz] (5) / 1 ms [1kHz] (6)
0,01 ms
Ch 0 ... Ch1: Process alarm overow disabled (0) / enabled (1) disabled
Ch 0 ... Ch1: Process alarm underow disabled (0) / enabled (1) disabled
Ch 0 ... Ch1: Process alarm comp. value disabled (0) / enabled (1) disabled
Ch 0 ... Ch1: Process alarm end value disabled (0) / enabled (1) disabled
Ch 0 ... Ch1: Counting mode count endless (0) / once - forward (1) /
once - backwards (2) / once - no main
direction (3) / periodic - forward (4) /
periodic - backwards (5) / periodic - no
main direction (6)
count endless